* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
2
// /
/
50-JC6dt3
FACTS
//
//
//
//
//
//
//
//
//
//
EPA Tier 3 Certified
Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
UL2200, CSA Listing Offered
Accepts Rated Load in One Step Per NFPA 110, Level 1
All engine-generator sets are prototype and factory tested
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
Custom Design for Any Application
4024HF285 Diesel Engine
- 2.4 Liter Displacement
- Electronic Unit Pump Injection
- 4-Cycle
Complete Range of Accessories
Permanent Magnet Generator (PMG) - Optional
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
//
Digital Control Panel(s)
- UL Recognized,
, NFPA 110
- Complete System Metering
- LCD Display
//
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
//
//
STANDARD EQUIPmENT
//
Engine
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130°C Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±1% Voltage Regulation
100% of Rated Load - One Step
3% Maximum Harmonic Content
Air Cleaner
Oil Pump
Full Flow Oil Filter
Jacket Water Pump
Thermostat
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Electric Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
//
digital Control Panel(s)
//
generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for up
to 10 seconds
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible
3
// /
/
50-JC6dt3
APPLICATION DATA
//
Engine
John Deere
4024HF285
4-Cycle
4 In-Line
146 (2.4)
3.4 (8.6)
4.1 (10.5)
18.2:1
1,800
JDEC
80 (60)
74 (55)
±.25%
60 Hz
Dry
//
Fuel Consumption
STANDBY
4.3 (16.3)
3.2 (12.1)
2.2 (8.3)
PRIME
3.7 (14)
2.9 (11)
2 (7.6)
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
//
Cooling - radiator System
STANDBY
122 (50)
0.5 (0.12)
26 (100)
1,988 (34.9)
608 (10.7)
510 (9)
PRIME
122 (50)
0.5 (0.12)
26 (100)
1,560 (27.4)
484 (8.5)
420 (7.4)
Ambient Capacity of Radiator: °F (°C)
Maximum Allowable Static
Pressure on Rad. Exhaust: in. H
2
0 (kPa)
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Rejection to Air to Air: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
//
Liquid Capacity (Lubrication)
//
Air requirements
STANDBY
151 (4.3)
4,511 (128)
PRIME
140 (4)
4,511 (128)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
2.1 (7.9)
0.68 (2.6)
3 (11.4)
//
Electrical
12
750
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
Aspirating: *SCFM (m /min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m
3
/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m
3
/min)
3
1,150 (33)
948 (27)
* Air density = 0.0739 lbm/ft
3
(1.184 kg/m
3
)
//
Fuel System
3/8” NPT
3/8” NPT
10 (3)
Diesel #2
21.7 (82)
//
Exhaust System
STANDBY
1,062 (572)
419 (11.9)
30 (7.5)
16 (4)
PRIME
1,029 (554)
385 (10.9)
30 (7.5)
16 (4)
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m
3
/min)
Maximum Allowable
Back Pressure: in. H
2
0 (kPa)
Minimum Allowable
Back Pressure: in. H
2
0 (kPa)
4
// /
/
50-JC6dt3
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design.
System
OPU
dimensions (L x W x H)
82 x 34 x 50 in (2,080 x 860 x 1,270 mm)
Weight (less tank)
1,598 lb (725 kg)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
SOUND DATA
unit type
OPU w/Critical Grade Muffler (dBA)
Sound Attenuated Enclosure (dBA)
Measurements for sound data are taken at 23 ft (7 m).
2008年7月9日, CombOLED 研究项目的工作重点是开发出高性价比的生产工艺,以实现有机发光二极管 (OLED) 的量产。欧司朗光电半导体公司固态照明部主管 Bernhard Stapp 表示:“该项目由欧盟提供资金支持,欧司朗负责协调运作,旨在为推行新型照明光源应用创造必要的条件。”这包括采用性价比卓越的方法构建新型元件架构,从而生产出大幅面透明光源。作为 LED 市场的创新推...[详细]
UHF和HF都是一般的技术分类,不过每一类都有独立的支持协议。HF在13.56MHz频段更具有一致性,虽然国际业内行业标准很多。UHF RFID在858-960MHz频段已商业化。同时也有多种国际标准支持,包括EPC global Gen 2。 标签与读写器通过无线链接交换数据。链接可以通过适合任何频段的、具有不同读取范围和抗干扰性的EMF或RF场实现。HF RFID技术主要通过电磁场传送信...[详细]
ABI Research最近评选并公布了全球超高频无源和高频无源 RFID芯片的前十大制造商。 前十大超高频无源芯片制造商是: 前十大高频无源芯片制造商是: 超高频的得奖名单并不出人意外,因为实际上似乎总是前三家公司获得大订单。ABI分析家 Mike Liard称,ABI很容易就评选出 Alien、Avery,和 Raflatac为全球...[详细]