Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
9457 Multi-Conductor - Audio, Control and Instrumentation Cable
For more Information
please call
1-800-Belden1
General Description:
20 AWG stranded (7x28) tinned copper conductors, conductors cabled, PVC insulation, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
12
20
7x28
TC - Tinned Copper
Total Number of Conductors:
12
Insulation
Insulation Material:
Insulation Material
Wall Thickness (in.)
PVC - Polyvinyl Chloride 0.015
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride .035
Overall Cable
Overall Cabling Color Code Chart:
Number Color
1
2
3
4
5
6
7
8
9
10
11
12
White
Red
Green
Brown
Blue
Orange
Yellow
Purple
Gray
Pink
Tan (around Black)
Black
Overall Nominal Diameter:
0.338 in.
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-20°C To +80°C
80°C (UL AWM Style 2464)
77 lbs/1000 ft.
148 lbs.
3.500 in.
Page 1 of 3
10-30-2013
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
9457 Multi-Conductor - Audio, Control and Instrumentation Cable
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
AWM Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
CMG
CMG
UL Style 2464 (300 V 80°C)
Yes
Yes
Yes
Yes
04/01/2005
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
CSA Flame Test:
UL1685 FT4 Loading
FT4
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
27
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
10.7
Max. Operating Voltage - UL:
Voltage
300 V RMS (UL AWM Style 2464)
Max. Recommended Current:
Current
2.8 Amps per conductor @ 25°C
Put Ups and Colors:
Item #
9457 060100
9457 0601000
9457 060500
9457 0605000
Notes:
C = CRATE REEL PUT-UP.
Putup
100 FT
1,000 FT
500 FT
5,000 FT
Ship Weight
8.500 LB
81.000 LB
41.500 LB
420.000 LB
Color
CHROME
CHROME
CHROME
CHROME
C
C
Notes
Item Desc
12 #20 PVC FRPVC
12 #20 PVC FRPVC
12 #20 PVC FRPVC
12 #20 PVC FRPVC
Revision Number: 3
© 2013 Belden, Inc
All Rights Reserved.
Revision Date: 08-14-2012
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Page 2 of 3
10-30-2013
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
9457 Multi-Conductor - Audio, Control and Instrumentation Cable
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
10-30-2013