Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
85230 Multi-Conductor - Control and Instrumentation Cable, 2 Conductors Cabled
For more Information
please call
1-800-Belden1
General Description:
20 AWG stranded (7x28) TC conductors, conductors cabled, Tefzel® insulation, drain wire, overall Beldfoil
Aluminum-Kapton® shield (100% coverage), Tefzel® jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
2
20
7x28
TC - Tinned Copper
Total Number of Conductors:
2
Insulation
Insulation Material:
Insulation Trade Name Insulation Material
Tefzel®
Wall Thickness (in.)
ETFE - Ethylene Tetrafluoroethylene .015
Outer Shield
Outer Shield Material:
Type Outer Shield Material
Coverage (%)
Tape Aluminum-Kapton® Foil 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
22
Stranded
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Trade Name Outer Jacket Material
Tefzel®
Nom. Wall Thickness (in.)
ETFE - Ethylene Tetrafluoroethylene .020
Overall Cable
Overall Cabling Color Code Chart:
Color
Black
Red
Overall Nominal Diameter:
0.182 in.
Mechanical Characteristics (Overall)
Operating Temperature Range:
Non-UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-60°C To +150°C
150°C
25 lbs/1000 ft.
28 lbs.
2 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
Yes
Yes
Page 1 of 3
10-30-2013
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
85230 Multi-Conductor - Control and Instrumentation Cable, 2 Conductors Cabled
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Other Specification:
Yes
Yes
Yes
04/01/2005
Yes
Yes
Yes
Yes
NEMA HP3
Flame Test
UL Flame Test:
VW-1
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
53.000
Nom. Inductance:
Inductance (µH/ft)
0.190
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
31
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/ft)
59
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
9.3
Max. Operating Voltage - Non-UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
4 Amps per conductor @ 25°C
Notes (Overall)
Notes:
Tefzel and Kapton are DuPont trademarks.
Put Ups and Colors:
Item #
85230 3681000
85230 368500
Putup
1,000 FT
500 FT
Ship Weight
29.000 LB
14.500 LB
Color
CLEAR, TRANSPARENT
CLEAR, TRANSPARENT
Notes
C
C
Item Desc
2#20 TEFZEL FS TEFZEL
2#20 TEFZEL FS TEFZEL
Notes:
C = CRATE REEL PUT-UP.
Page 2 of 3
10-30-2013
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
85230 Multi-Conductor - Control and Instrumentation Cable, 2 Conductors Cabled
Revision Number: 3
© 2013 Belden, Inc
All Rights Reserved.
Revision Date: 08-23-2012
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
10-30-2013