RP
RP325 Series
RP325
3PHASE DELTA TO 300A
ROHS COMPLIANT
RADIUS POWER
Your Power Partner
3-Phase Delta Dual Stage Power Line Filter
SPECIFICATIONS
Operating Freq.
Usable Freq.
Max. Operating Voltage
Ambient Temperature
Climatic Category
Hipot Rating (L-G)
Terminals (-T)
:
:
:
:
:
:
:
50/60Hz
DC - 400Hz
480V +10%
-25 to 50C
25/100/21
3500VDC
S: 15/30/50A (M5)
80/100A (M6)
150/200A (M10)
300A (M12)
CSA, UR, EN60939
LEAKAGE CURRENT
Y-cap, nF
0
10
100
1000
2000
mA,
480V/60Hz
0
0.1
1
10
20
Safety Approvals
:
PART NUMBER/ ORDERING
RP325
-X
(Amps)
15
30
50
80
100
150
200
300
-Y
(Ycap, nF)
0
10
100
1000
2000
-T
S
Weight
LBS (KG)
Typ.
4.7 (2.1)
4.7 (2.1)
4.7 (2.1)
9.5 (4.3)
18.0 (8.2)
18.0 (8.2)
18.0 (8.2)
25.0 (11.3)
SCHEMATIC
Note:
Use any combination of -Y with any -X (Amps) rating
e.g. RP325-200-1000-S (200 Amps with 1000nF Ycap)
www.radiuspower.com
Reference purposes only.
Specifications are subject to change.
Consult factory to verify specifications.
Engineering Assistance: engg@radiuspower.com
Sales:sales@radiuspower.com
61
RP
RP325
Typical Insertion Loss, dB (50/50ohm)
15/30/50Amp
15/30 Amp
FREQ (MHz)
CM (dB)
DM (dB)
.15
65
65
.5
75
75
1
75
75
10
58
75
30
40
70
RADIUS POWER
Your Power Partner
Mechanical Dimensions
50 Amp
FREQ (MHz)
CM (dB)
DM (dB)
.15
58
60
.5
70
70
1
70
75
10
58
70
30
40
60
80Amp
80 Amp
FREQ (MHz)
CM (dB)
DM (dB)
.15
54
55
.5
65
60
1
65
60
10
55
50
30
40
38
100 Amp
FREQ (MHz)
CM (dB)
DM (dB)
.15
70
55
.5
75
70
1
75
70
10
58
60
30
30
30
100/150/200Amp
150 Amp
FREQ (MHz)
CM (dB)
DM (dB)
.15
65
50
.5
70
65
1
70
70
10
55
60
30
30
30
300Amp
1
60
70
10
50
60
30
35
30
200 Amp
FREQ (MHz)
CM (dB)
DM (dB)
.15
60
50
.5
65
65
300 Amp
FREQ (MHz)
CM (dB)
DM (dB)
.15
60
55
.5
65
55
1
60
55
10
48
50
30
40
30
TYPICAL TOLERANCE: +/-0.02 (0.50)
Reference purposes only.
Specifications are subject to change.
Consult factory to verify specifications.
www.radiuspower.com
62
Engineering Assistance: engg@radiuspower.com
Sales:sales@radiuspower.com