Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
88118 Multi-Conductor - Low Cap. Computer Cable for EIA RS-232/422/485 Applications
For more Information
please call
1-800-Belden1
Description:
24 AWG stranded (7x32) tinned copper conductors, plenum, foam FEP insulation, twisted pairs, overall
Beldfoil shield (100% coverage), 24 AWG stranded TC drain wire, fluorocopolymer jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors # Pairs AWG Stranding Conductor Material
1
18
24
7x32
TC - Tinned Copper
Insulation
Insulation Material:
Insulation Material
FFEP - Foam Fluorinated Ethylene Propylene
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material
Beldfoil®
Coverage (%)
Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
24
7x32
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVDF - Fluorocopolymer
Overall Cable
Overall Nominal Diameter:
12.243 mm
Pair
Pair Color Code Chart:
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Color
White/Blue & Blue/White
White/Orange & Orange/White
White/Green & Green/White
White/Brown & Brown/White
White/Gray & Gray/White
Red/Blue & Blue/Red
Red/Orange & Orange/Red
Red/Green & Green/Red
Red/Brown & Brown/Red
Red/Gray & Gray/Red
Black/Blue & Blue/Black
Black/Orange & Orange/Black
Black/Green & Green/Black
Black/Brown & Brown/Black
Black/Gray & Gray/Black
Yellow/Blue & Blue/Yellow
Yellow/Orange & Orange/Yellow
Page 1 of 3
02-24-2012
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
88118 Multi-Conductor - Low Cap. Computer Cable for EIA RS-232/422/485 Applications
18
Yellow/Green & Green/Yellow
Single Conductor White
Mechanical Characteristics (Overall)
Operating Temperature Range:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius (Install)/Minor Axis:
-20°C To +150°C
186.918 Kg/Km
902.985 N
127 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
CMP
CMP
Yes
Yes
Yes
04/01/2005
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
C(UL) Flame Test:
NFPA 262
FT6
Plenum/Non-Plenum
Plenum (Y/N):
Yes
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
100
Nom. Inductance:
Inductance (µH/m)
0.68901
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
42.489
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
76.4473
Nominal Velocity of Propagation:
VP (%)
78
Nominal Delay:
Delay (ns/m)
4.2653
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
78.744
Page 2 of 3
02-24-2012
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
88118 Multi-Conductor - Low Cap. Computer Cable for EIA RS-232/422/485 Applications
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
36.091
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
1.1 Amps per conductor @ 25°C
Related Documents:
No related documents are available for this product
Put Ups and Colors:
Item #
88118 0081000
88118 008500
Notes:
C = CRATE REEL PUT-UP.
Putup
305 MT
152 MT
Ship Weight
67.132 KG
32.205 KG
Color
GRAY
GRAY
Notes
C
C
Item Desc
18#24 PR + 1#24 FS SOLEF
18#24 PR + 1#24 FS SOLEF
Revision Number: 1
© 2012 Belden, Inc
All Rights Reserved.
Revision Date: 05-14-2007
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
02-24-2012