Fused, dead front disconnect switches . . . . . . . . . . . 337
Disconnects
RED
indicates
NEW
information
307
Disconnects
Safety Module™ fused disconnect switch
SM363 _ _
Cooper Bussmann
®
Safety Module™
Specifications
Description:
A fused disconnect featuring enhanced safety
features and use of the Cooper Bussmann
®
CUBEFuse
®
.
Optional rejection kits prevent overfusing 30 and 60 amp
circuits. Padlockable handle and door interlock provide safety
during maintenance procedures. Viewing window permits
viewing CUBEFuse permanent fuse indication status
without opening the door.
Poles:
3
Enclosures:
NEMA 1, 3R, 12 and 4X
Ratings:
Volts: — 600Vac
Amps: — 0-100A
SCCR: — 50kA
Agency Information:
CE, UL Listed and cUL Listed.
Features and Benefits
•
easyID
™ fuse viewing window allows maintenance
personnel to quickly identify open fuses — without opening
the enclosure.
• Wide amp range in one unit provides installation flexibility —
one Safety Module™ covers 1-100A applications.
• Rejection kits prevent overfusing 30A and 60A circuits.
• Optional internal safety barrier covers all energized parts to
provide added protection against electrical hazards — even
with the enclosure door open.
Accessories
• Optional internal safety barriers
• Solid neutral terminal
• Auxiliary contacts
• Rejection kits for 30 and 60 amp applications
Catalog Numbers
Catalog
Numbers*
SM363FG
SM363FR
SM363FD
SM363FX
Amp
Rating
100
100
100
100
NEMA
Enclosure
1
3R
12
4XSS
Max. Hp Rating
240V
480V
600V
20
40
50
20
40
50
20
40
50
20
40
50
Dimensions (in)**
Height
Width Depth
16
8
5
16
12
5
16
10
6
16
12
6
SCCR
50kA
50kA
50kA
50kA
* For safety barrier/rejection plate, add the suffix “B” to the catalog number, then add either; 1 for 30A, 2 for 60A or 3 for 100A. Example: SM363FGB3.
NEMA 1 enclosures also available in gray. To order, place suffix “G” to the end of catalog number. Example: SM363FGG.
NEMA 3R & 12 only available in gray.
** Does not include mounting tabs or handle. See Data Sheet for full dimensional data.
308
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Disconnects
Safety Module™ fused disconnect switch
High Visibility
Safety Yellow
Easy to locate and
identify disconnect
means. Also available
in standard gray.
Padlockable Handle
With up to three
padlocks to
protect maintenance
personnel.
Door Interlock
Prevents opening door
while energized, but can
be overridden for testing
or inspection.
Positive Opening Operation
Contacts are opened and closed by a
driven mechanism (not springs) so the switch
cannot reach the “OFF” position unless the
contacts are truly open.
Optional Safety Barrier
Covers energized parts to provide added
protection against electrical hazards.
CUBEFuse™
• Class J time-delay electrical performance.
•
easyID™
permanent replace fuse indication
to quickly determine fuse condition.
• Finger-safe test points allow testing
voltage without exposure to energized
conductors.
Fuse Base
Accepts 1-100A fuses
(rejection kits available).
NEMA 1, 3R, 12 & 4X
Enclosures
Meet most application
requirements.
Viewing Window
Quick identification of fuse condition —
without opening the door.
Conduit Knockouts
For easy installation.
Field Installed Accessories
• Solid Neutral terminal
• Auxiliary contacts
• Internal lockable handle
• Rejection kit for 30 and 60 amp applications
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
309
Disconnects
Coordination Module™ fused lighting and
appliance panelboard
Type EP
Cooper Bussmann
®
Coordination Module™
Specifications
Description:
A fused lighting and appliance panelboard for
branch circuit applications. Specifically designed to meet the
2005 NEC
®
Code requirements for selective coordination for
Emergency, Legally Required Standby and Essential Electrical
Systems per 700.27, 701.18, and 517.26 when properly coordi-
nated with the upstream overcurrent protective device feeder.
Circuits:
12, 24, 36, 42
Enclosure:
NEMA 1
Ratings:
Volts: — 120/208 or 277/480Vac
Branch Circuit Amps: — 0-30A
SCCR: — 100kA
Agency Information:
UL67, UL 50.
Features and Benefits
• Complies with the new 2005 NEC
®
Selective Coordination
Requirements for Emergency, Legally Required Standby and
Essential Electrical Systems per 700.27, 701.18, and 517.26
when properly coordinated with the upstream overcurrent
protective device feeder. Per the 2005 NEC
®
: Coordination
(Selective) is the localization of an overcurrent condition to
restrict outages to the circuit or equipment affected,
accomplished by the choice of overcurrent protective devices
and their ratings or settings.
• Ensures system uptime with the goal of safety of human life
during emergencies or for essential health care functions.
• Provides a fast and easy solution to meeting new coordination
Code requirements. Simply utilize published fuse selective
coordination ratios to select the correct upstream fuse ratings.
• Offers significant savings compared to other fused panels and
selectively coordinated circuit breaker systems.
Typical Applications
• Hospitals
• Schools
• Commercial and industrial facilities
Catalog Numbers
Catalog Numbers
EP2M23012GCC
EP2M23024GCC
EP2M23036GCC
EP2M23042GCC
EP4M23012GCC
EP4M23024GCC
EP4M23036GCC
EP4M23042GCC
Coordination Module*
Voltage
Rating
SCCR
120/208
100kA**
120/208
100kA**
120/208
100kA**
120/208
100kA**
277/480
100kA***
277/480
100kA***
277/480
100kA***
277/480
100kA***
Branch Circuit
Amp
Number of
Rating
Circuits
30
12
30
24
30
36
30
42
30
12
30
24
30
36
30
42
Dimensions (in)
Height Width Depth
36
28
5
3
⁄
4
38
28
5
3
⁄
4
48
28
5
3
⁄
4
48
28
5
3
⁄
4
36
28
5
3
⁄
4
36
28
5
3
⁄
4
48
28
5
3
⁄
4
48
28
5
3
⁄
4
Type
MLO
MLO
MLO
MLO
MLO
MLO
MLO
MLO
Main Device
Amp Rating
200
200
200
200
200
200
200
200
* Meets UL 67 (Panelboards) and UL 50 (Cabinets and Boxes).
** When protected by upstream LPN-RK 100A max. LPJ 200A max. or JJN 200A max., otherwise 10kA.
*** When protected by upstream LPN-RK 200A max. LPJ 200A max. or JJN 200A max., otherwise 14kA.
310
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Disconnects
Coordination Module™ fused lighting and
appliance panelboard
NEMA Type 1 Enclosure
With surface mount trim.
Ground Bar
Bolted with set screw terminations.
120/208V or 277/480V Main Lugs
With AGW 6-300Kcmil terminations.
Full-Sized Neutral Bar
With set-screw terminations.
Class CC Fuse Holders With
easyID
Neon Indicator
Provides ease of coordination with
superior overcurrent protection and
open fuse indication.
12 to 42 Circuits
Branch Circuit Breakers
Provide circuit isolation.
200A Copper Main Bus
Data Sheet: 1154
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp