Product data sheet
Characteristics
RHN412BA76
plug-in relay with suppressor - Zelio RHN -
instantaneous - 4 C/O - 24 V DC - 5A
Main
Range of product
Product or component
type
Device short name
Contacts type and com-
position
Contacts operation
Control circuit voltage
[Ithe] conventional en-
closed thermal current
Status LED
Control type
Coil interference sup-
pression
Zelio Relay
Plug-in relay
RHN
4 C/O
Instantaneous
Standard
24 V DC
5 A at <= 40 °C
Without
Manual control
With
Complementary
[Ui] rated insulation voltage
Operating position
Minimum switching capacity
Contact bounce time
Voltage drop
Average resistance
Switching time
Average consumption in W
Control circuit voltage limits
Drop-out voltage threshold
Time constant
Mechanical durability
Operating rate
Operating time
CAD overall width
CAD overall height
CAD overall depth
Terminals description ISO n°1
250 V
Any position
150 mVA / 1 V
150 mVA at 10 mA
<= 10 ms
<= 100 V for 3 A at 24 V
30 mOhm at 20 °C
1.2...4 ms for de-energisation/energisation
1...4 ms for energisation/de-energisation
1.6 W at 20 °C
0.8...1.1 Uc conforming to IEC 60255
0.1...0.3 Uc
15 ms for closed contact(s)
12 ms for open contact(s)
20000000 cycles
<= 6 cyc/mn
2...7 ms between de-energisation of coil and closing of NC contact at 20 °C
10...20 ms between energisation of coil and closing of NO contact at 20 °C
33 mm
43 mm
54 mm
(11-12-14)OC
(21-22-24)OC
(31-32-34)OC
(41-42-44)OC
(A1-A2)CO
0.09 kg
Product weight
May 11, 2016
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Environment
Standards
BS 4794
IEC 60255
NF C 45-250
VDE 0435
ASE
BV
CSA
EDF
UR
USSR
TC
2500 V
-5...40 °C conforming to IEC 60255
-40...70 °C
6 gn (f = 10...55 Hz) conforming to NF C 20-616
6 gn (f = 10...55 Hz) conforming to IEC 60068-2-6
50 gn for 11 ms conforming to NF C 20-608
Product certifications
Protective treatment
Dielectric strength
Ambient air temperature for operation
Ambient air temperature for storage
Vibration resistance
Shock resistance
2