RP
RP692 Series
RP692
DC TO 2500A &1200V
CHASSIS MOUNT FILTER
INVERTER APPLICATION
ROHS COMPLIANT
RADIUS POWER
Your Power Partner
High Voltage/High Current DC Power Line Filter
SPECIFICATIONS
Max. Operating Voltage
Ambient Temperature
Climatic Category
Hipot Rating (L-G)
Terminals (-T)
:
:
:
:
:
1200VDC
-25 to 60C
25/100/21
4700VDC
S: 25/50A (M5)
75A (M6)
100A (M8)
150A (M10)
B: 250A (5x20)
400A (6x25)
600A (8x25)
800/1000A (8x40)
1500A (10x60)
2500A (15x70)
cURus, EN60939
FREQ (MHz)
CM(dB)
DM(dB)
TYPICAL INSERTION LOSS, dB
(50/50ohm)
.15
65
65
.5
1.0
55
50
10
45
35
75
70
30
40
30
Safety Approvals
:
PART NUMBER/ ORDERING
RP692
-X
-Y
(Amps) (Ycap, nF)
25
50
75
100
150
250
400
600
800
1000
1500
2500
B
100
1000
2000
S
-T
Weight
LBS (KG)
Typ.
3.0 (1.4)
5.5 (2.5)
5.5 (2.5)
8.5 (3.9)
13.0 (5.9)
13.0 (5.9)
17.0 (7.7)
17.0 (7.7)
18.0 (8.2)
18.0 (8.2)
18.0 (8.2)
60.0 (27.2)
SCHEMATIC
Note:
Use any combination of -Y with any -X (Amps) rating
e.g. RP692-25-100-S (25 Amps with 100nF Y-cap)
Reference purposes only.
Specifications are subject to change.
Consult factory to verify specifications.
www.radiuspower.com
Engineering Assistance: engg@radiuspower.com
Sales:sales@radiuspower.com
145
RP
RP692
Mechanical Dimensions
25 Amp
RADIUS POWER
Your Power Partner
50/75 Amp
100 Amp
150 Amp
TYPICAL TOLERANCE: +/-0.02 (0.50)
www.radiuspower.com
Reference purposes only.
Specifications are subject to change.
Consult factory to verify specifications.
Engineering Assistance: engg@radiuspower.com
Sales:sales@radiuspower.com
146
RP
RP692
Mechanical Dimensions
250 Amp
RADIUS POWER
Your Power Partner
400/600 Amp
250 Amp BUSBAR DETAIL
400/600 Amp BUSBAR DETAIL
400 Amp BUSBAR: 6x25
600 Amp BUSBAR: 8x25
TYPICAL TOLERANCE: +/-0.02 (0.50)
www.radiuspower.com
Reference purposes only.
Specifications are subject to change.
Consult factory to verify specifications.
Engineering Assistance: engg@radiuspower.com
Sales:sales@radiuspower.com
147
RP
RP692
Mechanical Dimensions
800/1000 Amp BUSBAR DETAIL
800/1000 Amp
RADIUS POWER
Your Power Partner
1500 Amp BUSBAR DETAIL
1500 Amp
2500 Amp BUSBAR DETAIL
2500 Amp
TYPICAL TOLERANCE: +/-0.02 (0.50)
www.radiuspower.com
Reference purposes only.
Specifications are subject to change.
Consult factory to verify specifications.
148
Engineering Assistance: engg@radiuspower.com
Sales:sales@radiuspower.com
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Astrodyne TDI
:
RP692-25-2000-S RP692-150-2000-S RP692-100-2000-S RP692-600-2000-B RP692-50-2000-S RP692-75-2000-
S RP692-1000-2000-B RP692-400-2000-B RP692-800-2000-B RP692-250-2000-B RP692-1500-2000-B RP692-
2500-2000-B RP692-25-100-S