Device coupler for Foundation Fieldbus and PROFIBUS PA expansions with terminal connections for 4 spurs
connected to Fieldbus end devices.
Your advantages
Built-in short-circuit protection
The TBUS routes the fieldbus data from the trunk line modules to the extension modules
Recommended for high-density control cabinet installations
LEDs indicate the power and error state
Power is supplied to the device couplers via the TBUS
Key Commercial Data
Packing unit
GTIN
GTIN
4046356298711
1 pc
Technical data
Dimensions
Width
Height
Depth
17.5 mm
94.3 mm
70.4 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Degree of protection
-40 °C ... 70 °C
-40 °C ... 85 °C
IP20
Serial interface
Interface 1
Connection method
Foundation Fieldbus and PROFIBUS PA Segment
Pluggable COMBICON screw connection for each spur
11/05/2018 Page 1 / 3
https://www.phoenixcontact.com/pi/products/2316019
Device coupler - FB-4SP - 2316019
Technical data
Serial interface
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Output nominal voltage
Output current
Maximum output current
Surge protection
Voltage drop trunk line / outputs
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
12
≤ 31 V (each spur)
≤ 43 mA (each spur)
≤ 58 mA (each spur)
Active if voltage exceeds 39 V (typ.) or 41 V (max.)
≤ 1.3 V
Power supply
Supply voltage range
Typical current consumption
9 V DC ... 31 V DC (input on trunk line side)
3.5 mA
General
Standards/regulations
IEC 60529, IEC 61158-2
NE21
EN 61326, EN 60068-2-27, EN 60068-2-6
Mounting position
Net weight
Color
ATEX
UL, USA/Canada
On horizontal DIN rail NS 35 in acc. with EN 60715
95.1 g
green
II 3 G Ex nA [nL] IIC T4 X
Class I, Zone 2, Group IIC T4
Class I, Div. 2, Groups A, B, C, D, T4
Standards and Regulations
Standards/regulations
IEC 60529, IEC 61158-2
NE21
EN 61326, EN 60068-2-27, EN 60068-2-6
Shock
Vibration (operation)
ATEX
UL, USA/Canada
15g, 11 ms
1g, 10 Hz ... 150 Hz
II 3 G Ex nA [nL] IIC T4 X
Class I, Zone 2, Group IIC T4
Class I, Div. 2, Groups A, B, C, D, T4
Drawings
11/05/2018 Page 2 / 3
https://www.phoenixcontact.com/pi/products/2316019
Device coupler - FB-4SP - 2316019
Dimensional drawing
SPUR 1
Circuit diagram
SPUR 3
94,3
85
17,5 7
S1+
S1-
S1S
I
I
S3+
S3-
S3S
SPUR 2
S2+
S2-
S2S
SPUR 4
I
I
S4+
S4-
S4S
70,4
S
F- F+
TBUS
Connection diagram: FB-4SP
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
11/05/2018 Page 3 / 3