Product datasheet
Characteristics
8501XO80V06
Main
Range of product
Relay type
Product or component type
[In] rated current
8501X
Control
Relay
10 A AC
5 A DC
[Uc] control circuit voltage
Control circuit voltage limits
Rated breaking capacity
440 V AC 50 Hz
480 V AC 60 Hz
0.85...1.1 Uc operational AC 50/60 Hz
6 A at: 120 V AC for inductive load control circuit per UL 508
3 A at: 240 V AC for inductive load control circuit per UL 508
1.5 A at: 480 V AC for inductive load control circuit per UL 508
1.2 A at: 600 V AC for inductive load control circuit per UL 508
10 A at: <= 600 V AC for resistive load control circuit per UL 508
1.1 A at: 125 V DC for inductive load control circuit per UL 508
0.55 A at: 250 V DC for inductive load control circuit per UL 508
0.2 A at: 301...600 V DC for inductive load control circuit per UL 508
4 A at: 125 V DC for resistive load control circuit per UL 508
0.8 A at: 250 V DC for resistive load control circuit per UL 508
60 A at: 120 V AC for inductive load control circuit per UL 508
30 A at: 240 V AC for inductive load control circuit per UL 508
15 A at: 480 V AC for inductive load control circuit per UL 508
12 A at: 600 V AC for inductive load control circuit per UL 508
10 A at: <= 600 V AC for resistive load control circuit per UL 508
1.1 A at: 125 V DC for inductive load control circuit per UL 508
0.55 A at: 250 V DC for inductive load control circuit per UL 508
0.2 A at: 301...600 V DC for inductive load control circuit per UL 508
4 A at: 125 V DC for inductive load control circuit per UL 508
0.8 A at: 250 V DC for resistive load control circuit per UL 508
148 VA 60 Hz
143 VA 50 Hz
23 VA 60 Hz
25 VA 50 Hz
15 ms pick-up
16 ms drop-out
8 NO 8 standard contact cartridges
Screw clamp terminals
AWG 18...AWG 12 copper
1.02...1.36 N.m control circuit screw terminals
Panel
3.5 in
2.23 in
5.16 in
[Icm] rated short-circuit making capacity
Inrush power in VA
Hold-in power consumption in VA
Operating time
Contacts type and composition
Electrical connection
AWG gauge
Tightening torque
Mounting support
Height
Width
Depth
Environment
ambient air temperature for operation
product certifications
-40...160 °F
UL listed file E78403 CCN NKCR
CSA LR60905 class 3211 03
1/2
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Complementary
Offer Sustainability
Green Premium product
Green Premium product
Compliant - since 1332 - Schneider Electric declaration Compliant - since 1332 - Schneider Electric declaration of conformity
of conformity
Reference not containing SVHC above the threshold
Available
Available
WARNING: This product can expose you to chemicals
including:
Reference not containing SVHC above the threshold
Available
Available
WARNING: This product can expose you to chemicals including:
Lead and lead compounds, which is known to the State Lead and lead compounds, which is known to the State of California to cause cancer
of California to cause cancer and birth defects or other and birth defects or other reproductive harm.
reproductive harm.
For more information go to www.p65warnings.ca.gov
For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period
18 months
2/2