RTEN
SERIES
Multipurpose Three-Phase Filter with Many Current Variations
■
FEATURES
●
●
●
●
■
SAFETY STANDARDS
UL1283
EN60939
File No. E62388(Up to 150A)
Licence Ref. No. SE/07115-5 (Up to 60A)
SE/07115-4 (80A to)
6 to 300A wide range lineup.
Small due to L1, light and thin.
Low-profile design.
Self-tightening screws and an open/close type cover
make wiring work easier.
Terminal block cover included for safety.
DIN rail installation compatible type is also available.
Compliant with RoHS directives.
●
●
●
■
PRODUCT IDENTIFICATION
RTEN ‒5 * * □
*
N/A:Standard Type
D
:DIN
rail installation compatible type (Up to 30A)
Rated current
Number indicating the rated voltage
Series name
■
CIRCUIT DIAGRAM
1
2
3
6
5
4
●
Conformity to RoHS Directive: This means that, in conformity with EU Directive 2002/95/EC, lead, cadmium, mercury, hexavalent chromium, and specific bromine-based
flame retardants, PBB and PBDE, have not been used, except for exempted applications.
All specifications are subject to change without notice.
●
002-02 / 20081024/ etl_rten
1
■
ELECTRICAL CHARACTERISTICS
Part No.
Rated
Rated
Withstand
voltage
current
voltage
(AC/DC)(AC/DC)
6A
10A
20A
30A
40A
50A
500V
60A
80A
100A
150A
200A
250A
300A
AC.2500V
60s
100MΩ
min.
2.5mA
max.
[250V/60Hz½
-25 to +85℃
5mA
max.
[500V/60Hz½
50℃
Insulation
resistance
Leakage
current
Operating
temperature
range
With
derating
over
DC
resistance
(mΩ)
145 max.
60 max.
25 max.
13 max.
10 max.
7 max.
5 max.
5 max.
4 max.
3 max.
2 max.
1.5 max.
1 max.
Attenuation frequency range (MHz)
Common mode
at 25dB
0.2 to 10
0.2 to 10
0.3 to 8
0.5 to 8
0.3 to 7
0.5 to 7
0.7 to 5
0.3 to 5
0.3 to 5
0.3 to 5
0.5 to 5
-
-
Weight
(kg)
0.36
0.36
0.56
0.56
1.10
1.10
1.10
3.90
4.20
6.50
9.20
8.70
8.30
Differential mode
at 25dB
0.2 to 30
0.2 to 30
0.2 to 30
0.2 to 30
0.2 to 30
0.2 to 30
0.2 to 30
0.2 to 5
0.2 to 5
0.2 to 5
0.2 to 5
0.2 to 5
0.2 to 5
at 10dB
-
-
-
-
-
-
-
-
-
-
-
0.5 to 10
0.5 to 10
RTEN-5006
RTEN-5010
RTEN-5020
RTEN-5030
RTEN-5040
RTEN-5050
RTEN-5060
RTEN-5080
RTEN-5100
RTEN-5150
RTEN-5200
RTEN-5250
RTEN-5300
[Between line [DC.500V/
to ground½
1min½
■
DERATINGS
120
Rated current (%)
100
80
60
40
20
0
–25
–10 0
10 20 30 40 50 60 70 80 90
Ambient temperature Ta (˚C)
2
■
SHAPES AND DIMENSIONS
RTEN-5006/5010
A
F
C
B
E
G
D
øH
RTEN-5020/5030/5040/5050/5060
A
F
C
B
E
G
D
øH
Dimensions in mm
Part No.
RTEN-5006
RTEN-5010
RTEN-5020
RTEN-5030
RTEN-5040
RTEN-5050
RTEN-5060
A
120
140
170
B
63
70
90
C
42
42
54
D
110
130
160
E
53
60
80
F
M4
M4
M5
G
M4
M4
M4
φH
4.5
4.5
4.5
Recommended clamping torque
M4:1.27N・m
M5:2.5N・m
Dimensions in mm
Part No.
RTEN-5080
RTEN-5100
RTEN-5150
RTEN-5200
RTEN-5250
RTEN-5300
A
267
290
390
B
161
190
195
C
85
88
103
D
247
270
370
E
135
164
84.5
F
M8
M8
M10
G
M6
M6
M8
φH
6.5
6.5
6.5
Recommended clamping torque
M6:4.8N・m
M8:7.64N・m
M10:11.8N・m
Dimensions in mm
Part No.
RTEN-5006D
A
B
C
D
E
F
G
H
I
J
K
3