AXL F AI4 I 1H
Axioline F analog input module, 4 current inputs,
integrated sensor supply
Data sheet
8658_en_02
1
Description
© PHOENIX CONTACT 2014-12-05
The module is designed for use within an Axioline F station.
It is used to acquire analog current signals.
Features
–
–
–
–
–
–
–
–
4 analog differential input channels for connecting cur-
rent signals
Connection of sensors in 2, 3, and 4-wire technology
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA,
±20 mA
Simultaneous scanning of all channels by means of si-
multaneous sampling
High crosstalk attenuation between the channels,
thanks to separate signal paths
Particularly robust against electromagnetic interference
Device type label stored
Diagnostic and status indicators
This data sheet is only valid in association with the UM EN AXL F SYS INST user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at
phoenixcontact.net/products.
AXL F AI4 I 1H
2
1
2
3
4
5
6
7
8
9
10
11
12
Table of contents
Description .............................................................................................................................. 1
Table of contents ..................................................................................................................... 2
Ordering data .......................................................................................................................... 3
Technical data ......................................................................................................................... 3
Tolerance data......................................................................................................................... 6
Internal circuit diagram ............................................................................................................ 7
Terminal point assignment....................................................................................................... 8
Connection examples .............................................................................................................. 8
Connection notes .................................................................................................................... 9
Local status and diagnostic indicators ................................................................................... 10
Process data.......................................................................................................................... 11
Significant values in various formats...................................................................................... 12
12.1 Significant values in IB IL format
............................................................................................ 12
12.2 Significant values in S7-compatible format
............................................................................... 12
12.3 Calculation of the measured value from the process data input value
.............................................. 13
Parameter, diagnostics and information (PDI) ....................................................................... 13
Standard objects ................................................................................................................... 14
14.1 Objects for identification (device rating plate)
............................................................................ 14
14.2 Object for multilingual capacity
.............................................................................................. 15
14.3 Object descriptions
............................................................................................................ 15
14.4 Diagnostics objects
............................................................................................................ 15
14.5 Objects for process data management
.................................................................................... 17
14.6 Objects for device management
............................................................................................ 18
Application objects ................................................................................................................ 19
15.1 Parameter table (0080hex: ParaTable)
.................................................................................... 19
15.2 Measured value in extended float format (0082hex: Measured Value Float)
..................................... 20
15.3 Minimum process data value (0083hex: PD Min)
....................................................................... 21
15.4 Maximum process data value (0084hex: PD Max)
...................................................................... 21
Device descriptions ............................................................................................................... 21
13
14
15
16
8658_en_02
PHOENIX CONTACT
2
AXL F AI4 I 1H
3
Ordering data
Type
AXL F AI4 I 1H
Description
Axioline F analog input module, 4 inputs: 0 - 20 mA, 4 - 20 mA, ±20 mA, 2,
3, and 4-conductor connection technology, integrated sensor supply (in-
cluding bus base module and connectors)
Order No.
2688491
Pcs. / Pkt.
1
Accessories
Axioline F bus base module for housing type H (Replacement item)
Axioline shield connection set (contains 2 busbar holders and 2 SK 5 shield
connection clamps)
Type
AXL F BS H
AXL SHIELD SET
Order No.
2700992
2700518
0829579
Pcs. / Pkt.
5
1
25
Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, un- ZB 20,3 AXL UNPRINTED
printed, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or
CMS-P1-PLOTTER (Marking)
Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual
labeling with M-PEN 0,8, X-PEN, or CMS-P1-PLOTTER (Marking)
Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK
ROLL, THERMOMARK ROLL X1, THERMOMARK X, THERMOMARK
S1.1, Mounting type: snapped into marker carrier, Lettering field: 35 x 28
mm (Marking)
ZBF 10/5,8 AXL UNPRINTED
EMT (35X28)R
0829580
0801602
50
1
Documentation
User manual, English, Axioline F: System and installation
Type
UM EN AXL F SYS INST
Order No.
-
-
Pcs. / Pkt.
-
-
User manual, English, Axioline F: Diagnostic registers, and error messages UM EN AXL F SYS DIAG
4
Technical data
Dimensions (nominal sizes in mm)
35
54
122,4
Width
Height
Depth
Note on dimensions
126,1
35 mm
126.1 mm
54 mm
The depth is valid when a TH 35-7.5 DIN rail is used (according to EN 60715).
General data
Color
Weight
Ambient temperature (operation)
Ambient temperature (storage/transport)
traffic grey A RAL 7042
145 g (with connectors and bus base module)
-25 °C ... 60 °C
-40 °C ... 85 °C
8658_en_02
PHOENIX CONTACT
3
AXL F AI4 I 1H
General data
Permissible humidity (operation)
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
Degree of protection
Protection class
Mounting position
5 % ... 95 % (non-condensing)
5 % ... 95 % (non-condensing)
70 kPa ... 106 kPa (up to 3000 m above sea level)
70 kPa ... 106 kPa (up to 3000 m above sea level)
IP20
III, IEC 61140, EN 61140, VDE 0140-1
Any (no temperature derating)
Connection data
Designation
Connection method
Conductor cross section solid / stranded
Conductor cross section [AWG]
Stripping length
Axioline F connector
Push-in technology
0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
24 ... 16
8 mm
Interface Axioline F local bus
Connection method
Transmission speed
Bus base module
100 MBit/s
Communications power
Communications power U
Bus
Current consumption from U
Bus
5 V DC (via bus base module)
typ. 120 mA, max. 150 mA
I/O supply
Supply of analog modules U
A
Maximum permissible voltage range
Current consumption from U
A
24 V DC (I/O supply and sensor supply)
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
typ. 38 mA (I
IS
= 0 mA)
max. 45 mA (I
IS
= 0 mA)
typ. 118 mA (I
IS
= 4 x 20 mA (nominal load))
max. 125 mA (I
IS
= 4 x 20 mA (nominal load))
typ. 238 mA (I
IS
= 4 x 50 mA (full load))
max. 245 mA (I
IS
= 4 x 50 mA (full load))
Electronic (35 V, 0.5 s)
Polarity protection diode
Suppressor diode
Surge protection
Protection against polarity reversal
Transient protection
Total power consumption of the module
Power consumption
typ. 1.5 W (at U
Bus
and U
A
), max. 1.83 W (at U
Bus
and U
A
)
Analog inputs
Number of inputs
Connection method
Connection method
Current input signal
Resolution A/D
A/D conversion time
Limit frequency (3 dB)
Measured value representation
Data formats
Process data update
Input filter
Precision
max. 4 (differential inputs, current)
Push-in technology
2, 3, 4-wire (shielded)
0 mA ... 20 mA , 4 mA ... 20 mA , -20 mA ... 20 mA
16 bit
31.25 µs
30 Hz , 12 kHz
16 bits (15 bits + sign bit)
IB IL, S7-compatible
160 µs
30 Hz, 12 kHz and mean-value generation (can be parameterized)
0.1 % (of measuring range final value for active mean-value generation and 30 Hz
filter)
PHOENIX CONTACT
8658_en_02
4
AXL F AI4 I 1H
Analog inputs
Transient protection of inputs
Input resistance current input
Open circuit response
Overload protection
Suppressor diode
104
Ω
(typical)
Going to 0 mA; open-circuit detection from 4 mA ... 20 mA
No; ±5.2 V DC, maximum, I
max
= 50 mA
Configuration and parameter data in a PROFIBUS system
Required parameter data
Need for configuration data
7 Byte
6 Byte
Electrical isolation/isolation of the voltage areas
Test section
5 V communications power (logic), 24 V supply (I/O)
5 V supply (logic)/analog inputs
5 V supply (logic)/functional earth ground
24 V supply (I/O)/analog inputs
24 V supply (I/O) / functional earth ground
Analog inputs/functional earth ground
Test voltage
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
Continuous shock according to EN 60068-2-27/IEC 60068-2-27
5g
30g
10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4
Transient surge voltage (surge) EN 61000-4-5/IEC 61000-4-5
Conducted interference EN 61000-4-6/IEC 61000-4-6
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022
Class B
Criterion B; 6 kV contact discharge, 8 kV air discharge
Criterion A; Field intensity: 10 V/m
Criterion B, 2 kV
Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); ±1 kV
to shielded I/O cables
Criterion A; Test voltage 10 V
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
8658_en_02
PHOENIX CONTACT
5