https://www.phoenixcontact.com/pi/products/2807955
Surge protection plug - CT 10-2PE/FS-24 - 2807955
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
LSA-PLUS plug (COMTRAB CT 10) with coarse/fine surge protection, for 10 floating signal circuits. Nominal
voltage: 24 V DC. Version: 10 double wires.
Your advantages
For use with CT-TERMIBLOCK and with LSA-PLUS and LSA-PROFIL disconnect and control strips
Multi-position, plug-in modular design
Applications include systems with higher signal voltages
Protection modules must be inserted in the correct direction
Combined protective circuits
Key Commercial Data
Packing unit
GTIN
GTIN
4017918104740
1 pc
Technical data
Dimensions
Height
Width
Depth
22 mm
111 mm
68.5 mm
Ambient conditions
Ambient temperature (operation)
Degree of protection
-25 °C ... 75 °C
IP20
General
Housing material
Flammability rating according to UL 94
Color
PBT
V0
black
10/27/2018 Page 1 / 4
https://www.phoenixcontact.com/pi/products/2807955
Surge protection plug - CT 10-2PE/FS-24 - 2807955
Technical data
General
Standards for cearances and creepage distances
Mounting type
Type
Direction of action
Arrester can be tested with CHECKMASTER from software version:
VDE 0110-1
IEC 60664-1
On CT-TERMIBLOCK and LSA-PLUS disconnect strip
LSA-PLUS module
Line-Line & Line-Earth Ground
From SW rev. 1.00
Protective circuit
IEC test classification
C1
C2
C3
D1
Nominal voltage U
N
Maximum continuous voltage U
C
Nominal current I
N
Operating effective current I
C
at U
C
Residual current I
PE
Nominal discharge current I
n
(8/20) µs (line-line)
Nominal discharge current I
n
(8/20) µs (line-earth)
Total surge current (8/20) µs
Max. discharge current I
max
(8/20) µs maximum (line-line)
Max. discharge current I
max
(8/20) µs maximum (line-earth)
Nominal pulse current Ian (10/1000) µs (line-line)
Output voltage limitation at 1 kV/µs (line-line) spike
Output voltage limitation at 1 kV/µs (line-earth) spike
Output voltage limitation at 1 kV/µs (line-line) static
Output voltage limitation at 1 kV/µs (line-earth) static
Residual voltage at I
n
(line-line)
Residual voltage with Ian (10/1000) µs (line-line)
Response time t
A
(line-line)
Response time t
A
(line-earth)
Input attenuation aE, sym.
24 V DC
40 V DC
28 V AC
1.5 A (75 °C)
≤ 5 µA (a-b)
≤ 1 µA (per path)
119 A (25 °C)
5 kA
10 kA
119 A (25 °C)
5 kA
23 A (25 °C)
≤ 70 V
≤ 650 V
≤ 60 V
≤ 650 V
≤ 85 V
≤ 65 V
≤ 1 ns
≤ 100 ns
0.1 dB (Typ. up to 2 MHz / 50 Ω)
0.1 dB (Typ. up to 1 MHz / 150 Ω)
0.1 dB (Typ. up to 400 kHz / 600 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
Cut-off frequency fg (3 dB), sym. in 600 Ohm system
Capacity (line-line)
Capacity (line-earth)
10 MHz (typ.)
4 MHz (typ.)
1 MHz (typ.)
1.1 nF (f=1 MHz / V
R
= 0 V)
1 pF
10/27/2018 Page 2 / 4
https://www.phoenixcontact.com/pi/products/2807955
Surge protection plug - CT 10-2PE/FS-24 - 2807955
Technical data
Protective circuit
Surge protection fault message
Impulse durability (line-earth)
none
C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 2.5 kA
Connection data
Connection method
Connection method IN
Connection method OUT
can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS
disconnect and switching strips
COMTRAB plug-in system
COMTRAB plug-in system
Standards and Regulations
Standards/regulations
Standards/specifications
IEC 61643-21
IEC 61643-21 2000
Drawings
Dimensional drawing
1.../19
Circuit diagram
1'.../19’
111
22
IN
OUT
68,5
2.../20
2'.../20’
Approvals
Approvals
Approvals
EAC / EAC
Ex Approvals
Approval details
10/27/2018 Page 3 / 4
https://www.phoenixcontact.com/pi/products/2807955
Surge protection plug - CT 10-2PE/FS-24 - 2807955
Approvals
EAC
RU C-
DE.A*30.B01561
EAC
EAC-Zulassung
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
10/27/2018 Page 4 / 4