https://www.phoenixcontact.com/pi/products/2800739
Type 2 surge protection plug - VAL-US 120 ST - 2800739
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection plug type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring, visual
fault warning. Design: 120 V AC.
Key Commercial Data
Packing unit
GTIN
GTIN
4046356644396
10 pc
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
52.4 mm
17.5 mm
55.3 mm
1 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
Shock (operation)
Vibration (operation)
IP20
-40 °C ... 80 °C
-40 °C ... 80 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification
EN type
Mode of protection
II
T2
T2
L-N
10/28/2018 Page 1 / 4
https://www.phoenixcontact.com/pi/products/2800739
Type 2 surge protection plug - VAL-US 120 ST - 2800739
Technical data
General
L-PEN
Mounting type
Color
Housing material
Degree of pollution
Flammability rating according to UL 94
Type
Number of positions
Arrester can be tested with CHECKMASTER from software version:
Surge protection fault message
on base element
jet black RAL 9005
PA 6.6
2
V-0
Male
1
From SW rev. 1.10
optical
Protective circuit
Nominal voltage U
N
Nominal frequency f
N
Maximum continuous voltage U
C
Residual current I
PE
Standby power consumption P
C
Nominal discharge current I
n
(8/20) µs
Maximum discharge current I
max
(8/20) µs
Short-circuit current rating I
SCCR
Voltage protection level U
p
Residual voltage U
res
120/208 V AC (TN)
60 Hz (50 Hz)
175 V AC
≤ 0.45 mA
≤ 80 mVA
20 kA
40 kA
25 kA
≤ 0.9 kV
≤ 0.9 kV (at I
n
)
≤ 0.75 kV (at 10 kA)
≤ 0.6 kV (at 5 kA)
≤ 0.55 kV (at 3 kA)
TOV behavior at U
T
Response time t
A
Max. backup fuse with branch wiring
208 V AC (5 s / withstand mode)
240 V AC (120 min / safe failure mode)
≤ 25 ns
125 A (gG)
Connection data
Connection method
VALVETRAB plug-in system
UL specifications
SPD Type
Maximum continuous operating voltage MCOV (L-N)
Nom. voltage
Mode of protection
Power distribution system
Nominal frequency
Measured limiting voltage MLV (L-N)
Nominal discharge current I
n
(L-N)
4CA
175 V AC
120 V AC
L-N
Single phase
50/60 Hz
1600 V
10 kA
10/28/2018 Page 2 / 4
https://www.phoenixcontact.com/pi/products/2800739
Type 2 surge protection plug - VAL-US 120 ST - 2800739
Technical data
Standards and Regulations
Standards/regulations
IEC 61643-11 2011
EN 61643-11 2012
Drawings
Dimensional drawing
52,4
44,8
17,5
Circuit diagram
Approvals
Approvals
Approvals
CSA / UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
Approval details
55,3
43,3
CSA
http://www.csagroup.org/services-industries/product-listing/
13631
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
10/28/2018 Page 3 / 4
https://www.phoenixcontact.com/pi/products/2800739
Type 2 surge protection plug - VAL-US 120 ST - 2800739
Approvals
EAC
RU C-
DE.A*30.B01561
cULus Recognized
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
10/28/2018 Page 4 / 4