https://www.phoenixcontact.com/us/products/2858962
Type 2 surge protection plug - VAL-MS 230-UD-ST - 2858962
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection connector type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring,
visual fault warning. Design: 230 V AC
The figure shows the VAL-MS 1000
PV-UD ST version
Key commercial data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
60.0 GRM
85363030
Germany
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
52.4 mm
17.5 mm
55.3 mm
1 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
Shock (operation)
Vibration (operation)
IP20
-40 °C ... 80 °C
-40 °C ... 80 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
25g
5g
General
Standards/specifications
IEC 61643-11 2011
10/21/2014 Page 1 / 5
https://www.phoenixcontact.com/us/products/2858962
Type 2 surge protection plug - VAL-MS 230-UD-ST - 2858962
Technical data
General
EN 61643-11 2012
IEC test classification
EN type
SPD design
Mode of protection
Mounting type
Color
Housing material
Pollution degree
Inflammability class according to UL 94
Type
Number of positions
Arrester can be tested with CHECKMASTER from software version:
Surge protection fault message
II
T2
T2
Voltage-limiting type
L-PEN
L-N
On base element
black
PA 6.6
2
V-0
DIN rail module, two-section, divisible
1
From SW rev. 1.10
Optical
Protective circuit
Nominal voltage U
N
Nominal frequency f
N
Maximum continuous operating voltage U
C
Residual current I
PE
Standby power consumption P
C
Nominal discharge current I
n
(8/20) µs
Maximum discharge current I
max
(8/20) µs
Short-circuit current rating I
SCCR
Voltage protection level U
p
Residual voltage U
res
240/415 V AC (TN)
240/415 V AC (TT)
50 Hz (60 Hz)
275 V AC
≤ 0.45 mA
≤ 120 mVA
20 kA
40 kA
25 kA
≤ 1.35 kV
≤ 1.35 kV (at I
n
)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
TOV behavior at U
T
Response time t
A
Max. backup fuse with branch wiring
335 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
≤ 25 ns
125 A AC (gG)
Connection data
10/21/2014 Page 2 / 5
https://www.phoenixcontact.com/us/products/2858962
Type 2 surge protection plug - VAL-MS 230-UD-ST - 2858962
Technical data
Connection data
Connection method
VALVETRAB plug-in system
UL specifications
UL class
Maximum continuous operating voltage MCOV (L-N)
Nom. voltage
Mode of protection
Power distribution system
Nominal frequency
Voltage protection rating VPR (L-N)
Nominal discharge current I
n
(L-N)
Type 4 SPD for Type 2 applications
275 V AC
230 V AC
L-N
1
50/60 Hz
1 kV
20 kA
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27140201
27130801
27130801
27130801
27130805
27130805
27130805
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000941
EC000941
EC000941
EC000941
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Approvals
Approvals
10/21/2014 Page 3 / 5
https://www.phoenixcontact.com/us/products/2858962
Type 2 surge protection plug - VAL-MS 230-UD-ST - 2858962
Approvals
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / GOST / KEMA-KEUR / CSA / ÖVE / CCA / IECEE CB Scheme / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
KEMA-KEUR
cUL Recognized
GOST
KEMA-KEUR
CSA
ÖVE
10/21/2014 Page 4 / 5
https://www.phoenixcontact.com/us/products/2858962
Type 2 surge protection plug - VAL-MS 230-UD-ST - 2858962
Approvals
CCA
IECEE CB Scheme
cULus Recognized
Drawings
Dimensioned drawing
52,4
44,8
17,5
Circuit diagram
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
55,3
43,3
10/21/2014 Page 5 / 5