Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 600DC-
PV/2+V - 2801163
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Lightning/surge arrester for 2-pos. isolated 600 V DC voltage systems, for DIN rail mounting, 3-pos. base
element, three plug-in temperature-monitored protective elements, status message on each plug.
Why buy this product
Increased safety, thanks to compliance with standard EN 50539-11
Reliable contact, thanks to integrated rotating latch
Easy replacement, thanks to plug-in arresters
Optimum inverter protection, thanks to low protection level
Efficient replacement of defective plugs, thanks to visual status indicator
Protection against mismatching, thanks to keyed plugs and base elements
Always the right arrester, thanks to universal type 1/type 2 protective components
Key Commercial Data
Packing unit
GTIN
GTIN
4046356714303
1 pc
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
89.8 mm
53.4 mm
65.7 mm (incl. DIN rail 7.5 mm)
3 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
IP20 (only when all terminal points are used)
-40 °C ... 80 °C
10/04/2018 Page 1 / 5
https://www.phoenixcontact.com/pi/products/2801163
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 600DC-
PV/2+V - 2801163
Technical data
Ambient conditions
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
Shock (operation)
Vibration (operation)
-40 °C ... 80 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
7.5g (5-500 Hz/2.5 h/XYZ)
General
IEC test classification
EN type
SPD failure behavior
Connection configuration
Installation location
Accessibility
Installation location of the disconnect device
Mode of protection
PV I / II
PV T1 / T2
T1 / T2
OCM (Open-circuit mode)
Y configuration
Inside
Accessible
Internal
(L+) - (L-)
(L+) - PE
(L-) - PE
Mounting type
Color
Housing material
Degree of pollution
Distance between live and grounded parts
Flammability rating according to UL 94
Type
Surge protection fault message
DIN rail: 35 mm
jet black RAL 9005
PA 6.6-FR
PBT-FR
2
8 mm
V-0
DIN rail module, two-section, divisible
optical
Additional descriptions
Note
The device is intended for touch proof installation in a housing. Ensure
that there is a gap of at least 8 mm between the active and grounded
parts in the connection area.
Protective circuit DC voltage side (DC)
Maximum continuous operating voltage U
CPV
Open circuit voltage U
OCSTC
Short-circuit current rating I
SCPV
Continuous operating current I
CPV
Rated load current I
L
Residual current I
PE
720 V DC
≤ 600 V DC
2000 A
< 20 µA
80 A
≤ 20 µA DC
≤ 350 µA AC
10/04/2018 Page 2 / 5
https://www.phoenixcontact.com/pi/products/2801163
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 600DC-
PV/2+V - 2801163
Technical data
Protective circuit DC voltage side (DC)
Standby power consumption P
C
Nominal discharge current (8/20) µs
Maximum discharge current I
max
(8/20) µs
Impulse discharge current (10/350) µs, charge
Impulse discharge current (10/350) µs, specific energy
Impulse discharge current (10/350) µs, peak value l
imp
Total discharge current I
total
(8/20) µs
Total discharge current I
total
(10/350) µs
Voltage protection level U
p
Residual voltage U
res
≤ 25 mVA
15 kA
40 kA
2.5 As
6.25 kJ/Ω
5 kA
40 kA
7 kA
≤ 2.6 kV
≤ 2.6 kV (at I
n
)
≤ 2 kV (at 5 kA)
≤ 2.3 kV (at 10 kA)
≤ 2.8 kV (at 20 kA)
≤ 3.1 kV (at 30 kA)
≤ 3.6 kV (at 40 kA)
Response time t
A
Insulation resistance R
iso
≤ 25 ns
> 5 GΩ (at 500 V DC)
Connection data
Connection method
Screw thread
Tightening torque
Stripping length
Conductor cross section flexible
Conductor cross section solid
Conductor cross section AWG
Connection method
Conductor cross section flexible
Screw connection
M5
3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
16 mm
1.5 mm² ... 25 mm²
1.5 mm² ... 35 mm²
15 ... 2
Fork-type cable lug
1.5 mm² ... 16 mm²
UL specifications
SPD Type
Maximum continuous operating voltage MCOV
Nominal voltage
Mode of protection
1
800 V DC
800 V DC
(L+) - (L-)
(L+) - G
(L-) - G
Power distribution system
Voltage protection rating VPR
Nominal discharge current I
n
DC PV
2 kV
20 kA
10/04/2018 Page 3 / 5
https://www.phoenixcontact.com/pi/products/2801163
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 600DC-
PV/2+V - 2801163
Technical data
UL specifications
Short-circuit current rating (SCCR)
50 kA
UL connection data
Conductor cross section AWG
Tightening torque
10 ... 2
30 lb
f
-in.
Standards and Regulations
Standards/regulations
EN 50539-11 2013
Drawings
Dimensional drawing
89,8
53,4
Circuit diagram
65,7
44
L+
L–
Approvals
Approvals
Approvals
KEMA-KEUR / EAC / UL Listed / cUL Listed / cULus Listed
Ex Approvals
Approval details
KEMA-KEUR
http://www.dekra-certification.com
71-102960
EAC
RU C-
DE.A*30.B01561
10/04/2018 Page 4 / 5
https://www.phoenixcontact.com/pi/products/2801163
Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 600DC-
PV/2+V - 2801163
Approvals
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm