https://www.phoenixcontact.com/us/products/2904960
Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Ex i measuring transducer power supply and input signal conditioner, HART. Transfers supplied or active 4 - 20
mA electrically isolated signals from the Ex area to two loads in the safe area. 4-way electrical isolation, PLd,
push-in technology.
The figure shows a version with a
screw connection
Product Features
Key commercial data
Packing unit
Custom tariff number
Country of origin
1 pc
85437090
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
12.5 mm
99 mm
114.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Maximum altitude
Permissible humidity (operation)
Noise immunity
-20 °C ... 60 °C (Any mounting position)
-40 °C ... 80 °C
≤ 2000 m
10 % ... 95 % (non-condensing)
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
05/18/2015 Page 1 / 6
https://www.phoenixcontact.com/us/products/2904960
Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960
Technical data
Ambient conditions
Degree of protection
IP20
Input data
Signal input
Current input signal
Transmitter supply voltage
Signal input
Current input signal
Voltage drop
Repeater power supply operation
4 mA ... 20 mA
> 16 V (20 mA)
> 15.1 V (23 mA)
Signal conditioner operation
4 mA ... 20 mA
approx. 3.9 V
Output data
Signal output
Current output signal
Load/output load current output
Output ripple
Output behavior in the event of an error
Signal output
Current output signal
Load/output load current output
Output ripple
Output behavior in the event of an error
Repeater power supply operation
4 mA ... 20 mA (active)
< 450 Ω (20 mA)
< 380 Ω (23 mA)
< 20 mV
rms
0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Signal conditioner operation
4 mA ... 20 mA (active)
< 450 Ω (20 mA)
< 380 Ω (23 mA)
< 20 mV
rms
0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Power supply
Designation
Supply voltage range
Max. current consumption
Power consumption
Repeater power supply operation
19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%))
< 75 mA (24 V DC / 20 mA)
< 1.45 W (24 V DC/ 20 mA)
Connection data
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
0.2 mm²
1.5 mm²
0.2 mm²
1.5 mm²
24
05/18/2015 Page 2 / 6
https://www.phoenixcontact.com/us/products/2904960
Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960
Technical data
Connection data
Conductor cross section AWG max.
Stripping length
Connection method
16
8 mm
Push-in connection
General
Maximum transmission error
Transmission error, typical
Maximum temperature coefficient
Step response (10-90%)
Status display
Inflammability class according to UL 94
Electromagnetic compatibility
Housing material
Color
Designation
Electrical isolation
< 0.1 % (of final value)
< 0.05 % (of final value)
< 0.01 %/K
< 600 µs (for 4 mA ... 20 mA step)
Green LED (PWR supply voltage)
V0
Conformance with EMC Directive 2004/108/EC
PA 66-FR
yellow
Input/output/power supply
300 V
rms
(Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation
Electrical isolation
Designation
Electrical isolation
Designation
Electrical isolation
Conformance
ATEX
Input/output
375 V (Peak value in accordance with EN 60079-11)
Input/power supply
375 V (Peak value in accordance with EN 60079-11)
Output 1/output 2
1.5 kV AC (50 Hz, 1 min., test voltage)
CE-compliant, additionally EN 61326
II (1) G [Ex ia Ga] IIC/IIB
II (1) D [Ex ia Da] IIIC
II 3 (1)G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx
[Ex ia Ga] IIC/IIB
[Ex ia Da]
Ex nA [ia Ga] IIC/IIB T4 Gc
UL, USA / Canada
UL 61010
Class I Div 2; IS for Class I, II, III Div 1
Data communication (bypass)
HART function
Protocols supported
Yes
HART
Safety data
05/18/2015 Page 3 / 6
https://www.phoenixcontact.com/us/products/2904960
Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960
Technical data
Safety data
Operation
Max. output voltage U
o
Max. output current I
o
Max. output power P
o
Group
Max. external inductivity L
o
Max. external capacity C
o
Group
Max. external inductivity L
o
Max. external capacity C
o
Safety-related maximum voltage U
m
Operation
Input voltage U
i
Input current I
i
Max. internal inductance L
i
Max. internal capacitance C
i
Repeater power supply operation
25.2 V
93 mA
587 mW
IIC
2 mH
107 nF
IIB
4 mH
820 nF
253 V AC (125 V DC)
Signal conditioner operation
≤ 30 V
≤ 150 mA
negligible
negligible
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27210120
27210120
27210120
27210120
27210120
27210120
27210120
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001485
EC001485
EC001485
EC002653
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
30211506
39121008
05/18/2015 Page 4 / 6
https://www.phoenixcontact.com/us/products/2904960
Repeater power supply - MACX PL-EX-RPSSI-2I-SP - 2904960
Classifications
UNSPSC
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
39121008
39121008
39121008
Approvals
Approvals
Approvals
UL Listed / cUL Listed / GL / cULus Listed
Ex Approvals
IECEx / ATEX / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
cUL Listed
GL
cULus Listed
Drawings
05/18/2015 Page 5 / 6