EMC filters
3-phase line reactor
for active infeed converters
Series/Type:
Date:
B86306A
April 2015
© EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company.
3-phase line reactor
for active infeed converters
B86306A
3-phase line reactors for converters
Rated voltage V
R
: 520 V AC
Rated current I
R
: 14 A to 418 A
Construction
3-phase line reactor for active infeed converters
Natural cooling
Features
Decoupling of powerline to PWM converter
Reduction of THD
Easy to install
Low weight
Compact design
Design complies with IEC 60076-6
Degree of protection
1)
:
IP20 (14 A)
IP10 (22 A ... 42 A)
IP00 (60 A ... 418 A)
UL approved insulation system T-EIS-CF1 E320370
Typical applications
Active infeed converters e.g. in
elevators
pumps
traction systems
conveyor systems
HVAC systems (heating, ventilation and air
conditioning)
Terminals
Finger-safe terminal blocks up to 42 A
Busbars from 60 A
Marking
Marking on component:
Manufacturer's logo, ordering code, rated current, rated
frequency, inductance, weight, date code
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
1) According to IEC 60529
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 2 of 12
3-phase line reactor
for active infeed converters
B86306A
Typical circuit diagram
Technical data and measuring conditions
Rated voltage V
R
Relative voltage drop u
k
in %
Converter output frequency f
P
Pulse frequency f
P
Rated current I
R
Test voltage V
test
Overload capability (thermal)
Max. dv/dt on reactor input
Insulation class
Climatic category (IEC 60068-1)
Approvals
Characteristics and ordering codes
I
R
A
u
k
%
R
typ1)
mΩ
41
12
12
9
4.9
3.8
3.4
2.1
1.75
1.08
0.73
L
R2)
µH
2270
1130
1130
770
460
460
310
340
230
160
120
P
L3)
W
33
35
42
70
75
85
170
177
285
390
495
Approx. weight
kg
4
12.5
16.8
18
33.8
37.9
40.3
72
91
145
173
Ordering code
520 V AC (50/60 Hz)
At I
R
; 50 Hz and 400 V AC
0 Hz ... 400 Hz
Up to 10 kHz (see table)
Referred to 40
°C
rated temperature
2500 V AC, 10 s (line/line)
2500 V AC, 10 s (lines/case)
1.5 I
R
for 1 min per hour
8 kV/µs (higher values can be approved individually)
F (155
°C)
25/100/21 ( 25
°C/+100 °C/21
days damp heat test)
Insulation system class 155 (F); T-EIS-CF1 UL 1446
V
R
= 520 V AC
14
4.3
22
3.4
29
4.5
42
4.4
60
3.8
74
4.6
110
4.6
143
6.6
209
6.5
304
6.6
418
6.8
B86306A0014R000
B86306A0022R000
B86306A0029R000
B86306A0042R000
B86306A0060S000
B86306A0074S000
B86306A0110S000
B86306A0143S000
B86306A0209S000
B86306A0304S000
B86306A0418S000
1) Typical value at 20
°C,
tolerance
±5%
2) At I
R;
tolerance
±10%
3) Typical values at I
R
, 50 Hz, 20
°C.
Varies with the pulse frequency and modulation mode.
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 3 of 12
3-phase line reactor
for active infeed converters
B86306A
Dimensional drawings
B86306A0014R000 (14 A)
General tolerances according to ISO 2768 cL
Dimensions in mm
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 4 of 12
3-phase line reactor
for active infeed converters
B86306A
B86306A0022R000 ... B86306A0042R000 (22 A ... 42 A)
Ordering code
B86306A0022R000
B86306A0029R000
B86306A0042R000
H
94
94
114
I
125
125
145
Q (mm
2
)
16
35
35
Mk (Nm)
2 ... 2.3
3.2 ... 3.7
3.2 ... 3.7
General tolerances according to ISO 2768 cL
Dimensions in mm
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 5 of 12