MINI MCR-RTD-UI-NC
Temperature transducers for resistance thermome-
ters and remote resistance-type sensors
Data sheet
105446_en_00
1
Description
© PHOENIX CONTACT 2013-01-14
Configurable 3-way isolated temperature transducer. The de-
Features
vice is suitable for the connection of resistance thermometers
– Configurable 3-way temperature transducer
and remote resistance-type sensors in 2, 3 and 4-wire con-
– Configurable via DIP switches for Pt 100 and Pt 1000
nection technology.
(IEC 751)
The measured values are converted into a linear current or
– Extended functionality configurable with free software
voltage signal.
– Approval for Ex-zone 2 (nA)
The device can either be configured via DIP switches or, with
extended functionality, via the S port using the software (FDT/ – Screw or spring-cage connection can be provided
DTM).
The device supports fault monitoring.
WARNING: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
Make sure you always use the latest documentation.
It can be downloaded from the product at
www.phoenixcontact.net/products.
This data sheet is valid for all products listed on the following page:
MINI MCR-RTD-UI-NC
2
1
2
3
4
5
Table of contents
Description .............................................................................................................................. 1
Table of contents ..................................................................................................................... 2
Ordering data .......................................................................................................................... 3
Technical data ......................................................................................................................... 4
Safety regulations and installation notes.................................................................................. 6
5.1
Installation notes
................................................................................................................. 6
5.2
Installation in the Ex area (zone 2)
............................................................................................ 6
Installation ............................................................................................................................... 7
6.1
Connection notes
................................................................................................................ 7
6.2
Structure
........................................................................................................................... 7
6.3
Block diagram
..................................................................................................................... 7
6.4
Power supply
...................................................................................................................... 8
6.5
Assembly
........................................................................................................................... 8
6.6
Connecting the wires
............................................................................................................ 9
Fault monitoring FM............................................................................................................... 10
Configuration ......................................................................................................................... 11
8.1
Configuration via DIP switches
.............................................................................................. 11
8.2
Connectable sensors
.......................................................................................................... 11
8.3
Configuration via software (FDT/DTM)
.................................................................................... 14
Diagnostic indicator ............................................................................................................... 14
6
7
8
9
105446_en_00
PHOENIX CONTACT
2
MINI MCR-RTD-UI-NC
3
Ordering data
Type
Order No.
2902849
Description
Pcs. / Pkt.
1
Configurable temperature transducer for the connection of 2, 3, and 4-con- MINI MCR-RTD-UI-NC
ductor resistance thermometers and resistance-type sensors. Can be con-
figured via DIP switches or, with extended functionality, using the software.
Screw connection, standard configuration.
Configurable temperature transducer for the connection of 2, 3, and 4-con- MINI MCR-RTD-UI-SP-NC
ductor resistance thermometers and resistance-type sensors. Can be con-
figured via DIP switches or, with extended functionality, using the software.
Spring-cage connection, standard configuration.
2902850
1
Accessories
Programming adapter with USB interface, for programming with software.
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply
the supply voltage to the T-connector. The FM power terminal block offers
the additional function of monitoring in combination with the fault monitor-
ing module. Screw connection.
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply
the supply voltage to the T-connector. The FM power terminal block offers
the additional function of monitoring in combination with the fault monitor-
ing module. Spring-cage connection.
The fault monitoring module is used to evaluate and report group errors
from the fault monitoring system and to monitor the supply voltages. The
error is reported via an N/O contact. Screw connection, standard configu-
ration.
The fault monitoring module is used to evaluate and report group errors
from the fault monitoring system and to monitor the supply voltages. The
error is reported via an N/O contact. Spring-cage connection, standard
configuration.
DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be
snapped onto NS 35/... DIN rails according to EN 60715
DIN rail power supply unit, primary-switched mode, slim design, output:
24 V DC / 1.5 A
Eight MINI analog signal converters with screw connection method can be
connected to a control system using a system adapter and system cabling
with a minimum of wiring and very low error risk.
MINI analog multiplexer, generates one analog output from 8 analog input
signals, for MINI analog module with screw connection.
Fold up transparent cover for MINI MCR modules with additional labeling
option using insert strips and flat Zack marker strip 6.2 mm
Label for extended marking of MINI MCR modules in connection with the
MINI MCR-DKL
Type
IFS-USB-PROG-ADAPTER
MINI MCR-SL-PTB-FM
Order No.
2811271
2902958
Pcs. / Pkt.
1
1
MINI MCR-SL-PTB-FM-SP
2902959
1
MINI MCR-SL-FM-RC-NC
2902961
1
MINI MCR-SL-FM-RC-SP-NC
2902962
1
ME 6,2 TBUS-2 1,5/5-ST-3,81 GN
MINI-SYS-PS-100-240AC/24DC/1.5
MINI MCR-SL-V8-FLK 16-A
2869728
2866983
2811268
10
1
1
MINI MCR-SL-MUX-V8-FLK 16
MINI MCR DKL
MINI MCR-DKL-LABEL
2811815
2308111
2810272
1
10
10
105446_en_00
PHOENIX CONTACT
3
MINI MCR-RTD-UI-NC
4
Input
Technical data
Configurable/programmable
Sensor type
Sensor input current
Max. permissible overall conductor resistance
Linear resistance measuring range
Temperature measuring range
Measuring range span
Connection method
Yes
Pt, Ni, Cu sensors
Approx. 200 µA
≤
25
Ω
(Per cable)
0
Ω
... 4000
Ω
(Minimum measuring span: 10% of the selected measuring range)
-200 °C ... 850 °C (Range depending on the sensor type)
min. 50 K
2, 3, 4-wire
Output
Voltage output signal
0 V ... 10 V
10 V ... 0 V
0 V ... 5 V
1 V ... 5 V
Approx. 12.3 V
0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
24.6 mA
Yes
10 kΩ
< 20 mV
PP
500
Ω
(at 20 mA)
Max. voltage output signal
Current output signal
Max. current output signal
Configurable/programmable
Load/output load voltage output
Ripple
Load/output load current output
Supply
Supply voltage range
9.6 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order
No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a
35 mm DIN rail according to EN 60715))
< 27 mA (at 24 V DC)
≤
700 mW (at I
OUT
= 20 mA, 9.6 V DC, load 500
Ω)
Typical current consumption
Power consumption
Diagnostic and status indicators
Status display
LED red
General data
Transmission error resistance thermometer
Transmission error resistance-type sensor
Maximum temperature coefficient
Step response (0–99%)
0.1% * 350 K / set measuring range; 0.1% > 350 K (Pt/Ni)
0.3% * 200 K / set measuring range; 0.3% > 200 K (Cu)
2
Ω
0.01 %/K
Typ. 200 ms (2-wire)
Typ. 500 ms (3-wire)
Typ. 500 ms (4-wire)
Basic insulation according to EN 61010
II
Any
IP20
2
50 V AC/DC
Electrical isolation
Surge voltage category
Mounting position
Degree of protection
Pollution degree
Rated insulation voltage
105446_en_00
PHOENIX CONTACT
4
MINI MCR-RTD-UI-NC
General data [...]
Test voltage, input/output/supply
Dimensions W / H / D
Type of housing
1.5 kV (50 Hz, 1 min.)
6.2 mm / 93.1 mm / 102.5 mm
PBT green
Connection data
Conductor cross section, solid
Conductor cross section, stranded
Stripping length
Screw connection
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
12 mm
Spring-cage conn.
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
8 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
-20 °C ... 65 °C
-40 °C ... 85 °C
5 % ... 95 % (no condensation)
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
When being exposed to interference, there may be minimal deviations.
Noise emission according to EN 61000-6-4
Conformance / approvals
Conformance
ATEX
UL, USA / Canada
UL, USA / Canada
Shipbuilding
CE-compliant
II 3 G Ex nA IIC T4 Gc X
UL 508 Recognized applied for
Class I, Div. 2, Groups A, B, C, D T5 applied for
GL applied for
105446_en_00
PHOENIX CONTACT
5