Relay module, with soldered-in miniature switching relay, contact (AgNi): Medium to large loads, 1 PDT, input
voltage 48 V DC
The illustration shows version
EMG 10-REL/KSR-G 24/1-LC, with
soldered-in miniature switching relay
Product Features
Safe isolation according to DIN EN 50178 between coil and contact
Integrated input circuit and interference suppression circuit
Packing unit
Custom tariff number
Country of origin
1 pc
85364190
Germany
Key commercial data
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
10.6 mm
75 mm
62.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-20 °C ... 40 °C
-20 °C ... 70 °C
10/22/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2963019
Relay Module - EMG 10-REL/KSR-G 48/21-LC - 2963019
Technical data
Coil side
Nominal input voltage U
N
Input voltage range in reference to U
N
Typical input current at U
N
Typical response time
Typical release time
Operating voltage display
Protective circuit
48 V DC
0.9 ... 1.1
8 mA
7 ms
11 ms
Yellow LED
Protection against polarity reversal Polarity protection diode
Free-wheeling diode Damping diode
Contact side
Contact type
Contact material
Maximum switching voltage
Maximum inrush current
Limiting continuous current
Interrupting rating (ohmic load) max.
Single contact, 1-PDT
AgNi
250 V AC/DC
8A
6A
140 W (at 24 V DC)
53 W (at 48 V DC)
45 W (at 60 V DC)
35 W (at 110 V DC)
55 W (at 220 V DC)
1500 VA (for 250 V AC)
General
Test voltage relay winding/relay contact
Operating mode
Mechanical service life
Standards/regulations
4 kV AC (50 Hz, 1 min.)
100% operating factor
Approx. 2 x 10 cycles
IEC 60664
EN 50178
IEC 62103
Rated surge voltage / insulation
Pollution degree
Surge voltage category
Mounting position
Assembly instructions
Basic insulation
2
III
any
In rows with zero spacing
7
Connection data
Connection method
Stripping length
Conductor cross section stranded min.
Screw connection
8 mm
0.2 mm²
10/22/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2963019
Relay Module - EMG 10-REL/KSR-G 48/21-LC - 2963019
Technical data
Connection data
Conductor cross section stranded max.
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG/kcmil max
Conductor cross section AWG/kcmil min.
Screw thread
2.5 mm²
0.2 mm²
4 mm²
12
24
M3
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27371102
27371102
27371001
27371001
27371001
27371001
27371001
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000196
EC000196
EC000196
EC000196
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30211916
39121515
39121515
39121515
39121515
Drawings
10/22/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2963019
Relay Module - EMG 10-REL/KSR-G 48/21-LC - 2963019
Connection diagram
14
12
11
11
Circuit diagram
13
14
A1
A2
A1
A2
Circuit diagram
12
A1
+
14
A2
-
11
11
Phoenix Contact 2014 © - all rights reserved