https://www.phoenixcontact.com/us/products/1534342
Bus system flat-type plug - SACCBP-M12MSB-2CON-
M16/0,5-910 - 1534342
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Bus system flush-type plug, PROFIBUS, 2-pos., M12, shielded, B-coded, rear/screw mounting with M16 thread,
with 0.5 m bus cable, 2 x 0.25 mm²
Packing unit
11
63.8 GRM
85444290
Germany
Key commercial data
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
Technical data
Dimensions
Length of cable
0.5 m
Ambient conditions
Ambient temperature (operation)
Degree of protection
-25 °C ... 85 °C (Plug / socket)
IP67
General
Rated current at 40°C
Rated voltage
Number of positions
Contact resistance
Insulation resistance
Coding
Standards/regulations
Status display
Surge voltage category
4A
60 V
2
≤ 3 mΩ
≥ 100 MΩ
B - inverse
M12 connector IEC 61076-2-101
No
II
08.11.2013 Page 1 / 5
https://www.phoenixcontact.com/us/products/1534342
Bus system flat-type plug - SACCBP-M12MSB-2CON-
M16/0,5-910 - 1534342
Technical data
General
Pollution degree
Test voltage
3
2500 V
Material
Inflammability class according to UL 94
Contact material
Contact surface material
Contact carrier material
Material, knurls
Sealing material
V0
CuZn
Ni/Au
PA 66
Nickel-plated brass
NBR
Cable
Cable type
Cable type (abbreviation)
UL AWM style
Conductor cross section
AWG signal line
Conductor structure signal line
Core diameter including insulation
Wire colors
Overall twist
Shielding
Optical shield covering
External sheath, color
External cable diameter D
Number of bending cycles
Bending radius
Traversing path
Traversing rate
Acceleration
Max. bending cycles
Bending radius
Traversing path
Traversing rate
Acceleration
Outer sheath, material
Material conductor insulation
PROFIBUS
910
21198 (80°C/300 V)
2x 0.25 mm² (signal line)
24
19x 0.13 mm
2.55 mm ±0.07 mm
Red, green
2 cores with 2 fillers to the core
Plastic-coated aluminum foil, tinned copper braided shield
85 %
Violet, RAL 4001
7.8 mm ± 0.2 mm
4000000
65 mm
4.5 m
3 m/s
3 m/s²
5000000
80 mm
4.5 m
3 m/s
3 m/s²
PUR
Foamed PE
08.11.2013 Page 2 / 5
https://www.phoenixcontact.com/us/products/1534342
Bus system flat-type plug - SACCBP-M12MSB-2CON-
M16/0,5-910 - 1534342
Technical data
Cable
Conductor material
Insulation resistance
Conductor resistance
Working capacitance
Wave impedance
Shield attenuation
Nominal voltage, cable
Test voltage Core/Core
Test voltage Core/Shield
Flame resistance
Other resistance
Ambient temperature (operation)
Tin-plated Cu litz wires
≥ 5 GΩ*km
157.2 Ω/km
30 nF
nom. 150 Ω ±10 % (3 MHz ... 20 MHz)
≤ 4.9 dB (at 16 MHz)
30 V
1500 V (50 Hz, 1 min.)
1500 V (50 Hz, 1 min.)
UL 1581, Sec. 1060 (FT-1)
IEC 60332-1
Low adhesion
-40 °C ... 80 °C (cable, fixed installation)
-30 °C ... 70 °C (cable, flexible installation)
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27140815
27140815
27143423
27143423
27143423
27449001
27449001
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001297
EC002061
EC002061
EC002061
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
31251501
31251501
31251501
08.11.2013 Page 3 / 5
https://www.phoenixcontact.com/us/products/1534342
Bus system flat-type plug - SACCBP-M12MSB-2CON-
M16/0,5-910 - 1534342
Classifications
UNSPSC
UNSPSC 12.01
UNSPSC 13.2
31251501
31251501
Approvals
Approvals
Approvals
GOST / GOST
Ex Approvals
Approvals submitted
Approval details
GOST
GOST
Drawings
08.11.2013 Page 4 / 5
https://www.phoenixcontact.com/us/products/1534342
Bus system flat-type plug - SACCBP-M12MSB-2CON-
M16/0,5-910 - 1534342
Dimensioned drawing
max.4,5
Schematic diagram
4
5
3
Ø16,1
1
2
13,5
+0,1
Pin assignment M12 male connector, 5-pos., B-coded, male side
Housing cutout for M16 fastening thread, mounting panel with feed-
through hole (alternatively with surface as protection against rotation)
Cable cross section
Dimensioned drawing
46,5
21
11
M16x1,5
PROFIBUS [910]
M12 flush-type plug
Circuit diagram
1
2
4
3
5
GN
RD
Contact assignment of the M12 plug
© Phoenix Contact 2013 - all rights reserved
http://www.phoenixcontact.com
SW19
M12x1
08.11.2013 Page 5 / 5