Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
2180LP Multi-Conductor - Media, Automation and Lighting Control
For more Information
please call
1-800-Belden1
General Description:
Lighting & Automation Cable, Plenum-CMP, 2-18 AWG bare copper conductors unshielded, FEP insulation
(power) and 1 (data) pair 22 AWG stranded bare copper, FEP insulation, Beldfoil®shield w drain,
Flamarrest® jacket.
Usage (Overall)
Suitable Applications:
Automation/Lighting Control
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors # Pairs AWG Stranding Conductor Material
1
2
22
18
7x30
7x26
BC - Bare Copper
BC - Bare Copper
4
Total Number of Conductors:
Insulation
Insulation Material:
Insulation Material
AWG
FEP - Fluorinated Ethylene Propylene 22
FEP - Fluorinated Ethylene Propylene 18
Inner Shield
Inner Shield Material:
Layer #
Inner Shield Trade Name Type Inner Shield Material
Coverage (%) Stranding Dia. (mm) Conductor Material
22 AWG Pair Beldfoil®
Inner Shield Drain Wire AWG:
AWG
24
Inner Shield Drain Wire Stranding:
Inner Shield Drain Wire Conductor Material:
7x32
TC - Tinned Copper
Tape Aluminum Foil-Polyester Tape 100
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Trade Name Outer Jacket Material
Flamarrest®
Outer Jacket Ripcord:
LS PVC - Low Smoke Polyvinyl Chloride
No
Overall Cable
Overall Nominal Diameter:
4.394 mm
Pair
Pair Color Code Chart:
Number Color
1
2
Purple & White
Red & Black
Mechanical Characteristics (Overall)
Operating Temperature Range:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
0°C To +60°C
32.740 Kg/Km
266.892 N
44.450 mm
Page 1 of 3
09-11-2017
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
2180LP Multi-Conductor - Media, Automation and Lighting Control
Min. Bend Radius/Minor Axis:
44.450 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
CMP
CMP
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
CSA Flame Test:
NFPA 262 Plenum Flame Test (UL910)(FT6)
FT6
Suitability
Suitability - Indoor:
Yes
Plenum/Non-Plenum
Plenum (Y/N):
Non-Plenum Number:
Yes
2180LA
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Description Capacitance (pF/m)
22 AWG Pair 82.025
Nom. Conductor DC Resistance:
Description DCR @ 20°C (Ohm/km)
22AWG
18AWG
52.824
21.327
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Description Current
22AWG
18AWG
3.8 Amps per conductor @ 25°C
7.2 Amps per conductor @ 25°C
Notes (Overall)
Notes:
Sequential footage marking every two feet.
Put Ups and Colors:
Item #
2180LP 0091000
2180LP 009250
2180LP 009500
Putup
1,000 FT
250 FT
500 FT
Ship Weight
28.000 LB
7.250 LB
16.000 LB
Color
WHITE
WHITE
WHITE
Notes
Item Desc
1 FS PR #22 + 2 #18 FEP FLRST
1 FS PR #22 + 2 #18 FEP FLRST
1 FS PR #22 + 2 #18 FEP FLRST
Revision Number: 0
© 2017 Belden, Inc
All Rights Reserved.
Revision Date: 04-08-2015
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 2 of 3
09-11-2017