Product catalogue | Electronics | Surge protection | Low-voltage supply | Class I lightning arrester with spark gap |
Sparkover gap
General ordering data
Order No.
Part designation
Version
EAN
Qty.
Product notes
Note, ordering data
Product description
Function
Note, accessories
8561260000
PU 1 TSG 35kA / 0,9kV
Surge protection for low-voltage supply, Rated
voltage: 230 V
4032248695171
1 pc(s).
Cross-connection QB 18-4 order no.
8619440000Cross-connection QB 18-6 order no.
8619450000
Class I lightning arrester with triggered sparkover
gap for industrial applications
Designation BZ18, PE PE PE PE PE, order no.
8619470000Designation BZ18, L1 L2 L3 N PE,
order no. 8619460000
35 mm²
25 mm²
10 mm²
4.5 Nm
Screw connection
Green LED
Installation housing
2
Screw connection
35 mm²
Clamped conductors
Rated cross-section for solid/flexible with ferrule
Stranded, max.
Stranded, min.
Tightening torque range
Type of connection
General data
Optical function display
Design
Pollution severity
Type of connection
Rated cross-section for solid/flexible with ferrule
-1-
Product catalogue | Electronics | Surge protection | Low-voltage supply | Class I lightning arrester with spark gap |
Sparkover gap
General data
solid
flexible
Flexible w. ferrule (DIN 46228-1)
stranded
Ambient temperature (operational)
Storage temperature
Note, accessories
10 ... 25 mm²
-40 ... 85°C
-40 ... 85°C
Designation BZ18, PE PE PE PE PE, order no.
8619470000Designation BZ18, L1 L2 L3 N PE,
order no. 8619460000
III
2
900 V
900 V
Green LED
230 V
230 V
260 V
Class I
T1
Requirements class B
35 kA with 17.5As charge
305 kJ/Ω
3 kA / 50 Hz
25 kA
≤ 1 µs
125 A gl
900 V
2.5 mA
AC
35 kA
50...60 Hz
35 mm²
10 mm²
35 mm²
91 mm
63 mm
18 mm
Insulation coordination acc. to EN 50178
Overvoltage category
Pollution severity
Interference voltage
On output side (L /N - PE) at max. discharge
current; smaller
On output side, smaller
Protective elements
Optical function display
Technical data
Rated voltage
Rated voltage (AC)
Max. continuous voltage, Uc (AC)
Requirements class, acc. to IEC 61643-1
Requirements class, acc. to EN 61643-11
Acc.to DIN VDE 0675-6
Lightning test current I imp (10/350 µs)
Specific energy, per path
Short-circuit current extinction without back-up
fuse
Short-circuit strength with max. back-up fuse
Sparkover time
Fuse, max.
Protection level Up (typical)
Leakage current at Un
AC/DC/UC
Discharge current, max. (10/350 µs)
Mains frequency at 250 Vmax
Dimensions
Clamping range, max.
Clamping range, min.
Clamping range, nom.
Length
Height
Width
-2-
Product catalogue | Electronics | Surge protection | Low-voltage supply | Class I lightning arrester with spark gap |
Sparkover gap
Approvals
Approvals institutes
Classifications
eClass 4.1
eClass 5.0
eClass 5.1
27-14-02-01
27-14-02-01
27-14-02-01
Similar products
Order No.
8561230000
8762020000
8561220000
8561250000
Part designation
PU 1 TSG 50kA / 1,5kV
PU 1 TSG 100kA/1,5 kV
PU1 TSG Plus 330 VAC 0,9kV
PU1 TSG Plus 440 VAC 1,5kV
Version
Surge protection for low-voltage supply, Rated voltage: 230 V
Surge protection for low-voltage supply, Rated voltage: 230 V
Surge protection for low-voltage supply, Rated voltage: 230 V
Surge protection for low-voltage supply, Rated voltage: 400 V
-3-