https://www.phoenixcontact.com/hq/products/2882417
Type 3 surge protection device - MNT-TELE E - 2882417
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Socket attachment plug with surge protection for the power supply and signal connection of a termination
device with analog or digital telecommunications interface (VDSL up to 46 Mbps). Cable is included.
Why buy this product
Easy operation
Thermal monitoring of the protective circuit
Compact protection for termination devices
Green LED - operating indicator for the power supply
Key Commercial Data
Packing unit
GTIN
GTIN
Custom tariff number
Note
4046356073486
85363010
Made to Order (non-returnable)
1 STK
Technical data
Dimensions
Height
Width
Depth
103 mm
63 mm
78 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-25 °C ... 75 °C
-25 °C ... 75 °C
General
Housing material
Flammability rating according to UL 94
PA 6
V-0
11/15/2016 Page 1 / 4
https://www.phoenixcontact.com/hq/products/2882417
Type 3 surge protection device - MNT-TELE E - 2882417
Technical data
General
Color
For country-specific use in
Mounting type
Design
Direction of action
jet black RAL 9005
NL, E, I, S, FIN, TR
Plugging into the mains socket
Attachment plug
L/N-PE & Signal Line-Earth Ground
Protective circuit, power supply
IEC test classification
EN type
Nominal voltage U
N
Arrester rated voltage U
C
(L-N)
Arrester rated voltage U
C
(L-PE)
Arrester rated voltage U
C
(N-PE)
Nominal frequency f
N
Rated load current I
L
Standby power consumption P
C
Residual current I
PE
Nominal discharge current I
n
(8/20) µs
Combination wave U
OC
Energy absorption symmetrical
Enery absorption, asymmetrical
Voltage protection level U
p
(L-N)
Voltage protection level U
p
(L-PE)
Voltage protection level U
p
(N-PE)
Response time (L-N)
Response time (L-PE)
Response time (N-PE)
Surge protection fault message
Max. required back-up fuse
III
T3
T3
230 V AC
275 V AC
360 V AC
360 V AC
50 Hz (60 Hz)
16 A (30 °C)
≤ 1 VA
≤ 5 µA
3 kA (> 5x)
4 kV
140 J (L-N)
220 J (L(N)-PE)
≤ 1.2 kV
≤ 1.5 kV
≤ 1.5 kV
≤ 25 ns
≤ 100 ns
≤ 100 ns
optical
16 A (gG / B / C)
Connection (protective circuit, power supply)
Connection method
Connection type IN
Connection type OUT
Grounding plug/socket
Grounding plug
Grounding socket
Protective circuit, information technology
Arrester rated voltage U
C
Rated current
Operating effective current I
C
at U
C
Residual current I
PE
200 V DC
150 mA (25 °C)
≤ 150 µA
≤ 2 µA
11/15/2016 Page 2 / 4
https://www.phoenixcontact.com/hq/products/2882417
Type 3 surge protection device - MNT-TELE E - 2882417
Technical data
Protective circuit, information technology
Insulation resistance R
iso
Nominal discharge current I
n
(8/20) µs (Core-Core)
Nominal discharge current I
n
(8/20) µs (Core-Earth)
Max. discharge current I
max
(8/20) µs
Voltage protection level U
p
(core-core)
Voltage protection level U
p
(core-ground)
Response time tA (Core-Core)
Response time tA (Core-Earth)
Cut-off frequency fg (3 dB), sym. in 100 Ohm system
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
Cut-off frequency fg (3 dB), sym. in 600 Ohm system
Capacity (Core-Core)
Capacity (Core-Earth)
Output voltage limitation at 1 kV/µs (wire-wire)
Residual voltage at I
n
(conductor-conductor)
Residual voltage at I
n
(conductor-ground)
Residual voltage with Ian (10/1000)µs (conductor-conductor)
Residual voltage with Ian (10/1000)µs (conductor-ground)
Impulse durability (conductor-conductor)
Impulse durability (conductor-ground)
≥ 1 MΩ
≥ 1 GΩ
1 kA
2.5 kA
2.5 kA
≤ 460 V (C2 - 1 kA)
≤ 350 V (C3 - 25 A)
≤ 900 V (C2 - 2 kA)
≤ 900 V (C3 - 100 A)
≤ 25 ns
≤ 100 ns
typ. 4 MHz
typ. 3 MHz
typ. 700 kHz
typ. 1 nF
typ. 5 pF
≤ 360 V
≤ 500 V
≤ 30 V
≤ 35 V
≤ 35 V
C2 - 2 kV / 1 kA
C3 - 25 A
C2 - 4 kV/2 kA
C3 - 100 A
D1 - 500 A
Alternating current carrying capacity (conductor-conductor)
Alternating current carrying capacity (conductor-ground)
Pulse reset time (conductor-conductor)
250 mA - 1 s
10 A - 1 s
≤ 15 ms
Power supply, general
Connection method
Connection type IN
Connection type OUT
RJ12
RJ12 female connector
RJ12 female connector
Connection, equipotential bonding, information technology
Connection method
Via protective contact plug
Standards (protective circuit, information technology)
IEC test classification
C1
C2
C3
11/15/2016 Page 3 / 4
https://www.phoenixcontact.com/hq/products/2882417
Type 3 surge protection device - MNT-TELE E - 2882417
Technical data
Standards (protective circuit, information technology)
D1
Drawings
Dimensional drawing
63,3
52,6
78,3
42
Circuit diagram
3
4
2
5 PE
N
L
Approvals
Approvals
Approvals
EAC
Ex Approvals
Approval details
EAC 7500651.22.01.00243
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
103,3