AXL F AI8 1F
Axioline F analog input module, 8 inputs,
2-wire connection method
Data sheet
7989_en_03
1
Description
© PHOENIX CONTACT 2015-07-03
The module is designed for use within an Axioline F station.
It is used to acquire analog voltage and current signals.
Features
–
–
–
–
–
–
Eight analog, bipolar input channels to connect either
voltage or current signals
Connection of sensors in 2-wire technology
Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, ±5 V
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA,
±20 mA
Device type label stored
Diagnostic and status indicators
This data sheet is only valid in association with the UM EN AXL F SYS INST user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at
phoenixcontact.net/products.
AXL F AI8 1F
2
1
2
3
4
5
6
7
8
9
10
11
12
Table of contents
Description .............................................................................................................................. 1
Table of contents ..................................................................................................................... 2
Ordering data .......................................................................................................................... 3
Technical data ......................................................................................................................... 3
Tolerance data......................................................................................................................... 6
Internal circuit diagram ............................................................................................................ 7
Terminal point assignment....................................................................................................... 7
Connection examples .............................................................................................................. 8
Connection notes .................................................................................................................... 8
Local status and diagnostic indicators ................................................................................... 10
Process data.......................................................................................................................... 11
Significant values in various formats...................................................................................... 12
12.1 Significant values in IB IL format
............................................................................................ 12
12.2 Significant values in S7-compatible format
............................................................................... 12
12.3 Calculation of the measured value from the process data input value
.............................................. 13
Parameter, diagnostics and information (PDI) ....................................................................... 13
Standard objects ................................................................................................................... 14
14.1 Objects for identification (device rating plate)
............................................................................ 14
14.2 Object for multilingual capacity
.............................................................................................. 15
14.3 Object descriptions
............................................................................................................ 15
14.4 Diagnostics objects
............................................................................................................ 16
14.5 Objects for process data management
.................................................................................... 18
Application objects ................................................................................................................ 19
15.1 Parameter table (0080hex: ParaTable)
.................................................................................... 19
15.2 Measured value in extended float format (0082hex: Measured Value Float)
..................................... 20
Device descriptions ............................................................................................................... 20
13
14
15
16
7989_en_03
PHOENIX CONTACT
2
AXL F AI8 1F
3
Ordering data
Type
AXL F AI8 1F
Description
Axioline?F analog input module, 8 inputs: 0 - 10 V, ±10 V, 0 - 20 mA,
4 - 20 mA, ±20 mA, 2-wire connection method (including bus base module
and connectors)
Order No.
2688064
Pcs./Pkt.
1
Accessories
Axioline F bus base module for housing type F (Replacement item)
Type
AXL F BS F
Order No.
2688129
2700984
2700518
0829579
Pcs./Pkt.
5
1
1
25
Axioline F connector set (for e.g., AXL F AI8 1F, AXL F AO8 1F) (Replace- AXL CNS 4L-O/D/UA/E1/E2
ment item)
Axioline shield connection set (contains 2 busbar holders and 2 SK 5 shield
connection clamps)
AXL SHIELD SET
Zack marker strip for Axioline F (device labeling), in 2 x 20.3 mm pitch, un- ZB 20,3 AXL UNPRINTED
printed, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or
CMS-P1-PLOTTER (Marking)
Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual
labeling with M-PEN 0,8, X-PEN, or CMS-P1-PLOTTER (Marking)
Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK
ROLL, THERMOMARK ROLL X1, THERMOMARK X, THERMOMARK
S1.1, Mounting type: snapped into marker carrier, Lettering field: 35 x 46
mm (Marking)
ZBF 10/5,8 AXL UNPRINTED
EMT (35X46)R
0829580
0801604
50
1
Documentation
User manual, English, Axioline F: System and installation
Type
UM EN AXL F SYS INST
Order No.
-
-
Pcs./Pkt.
-
-
User manual, English, Axioline F: Diagnostic registers, and error messages UM EN AXL F SYS DIAG
4
Technical data
Dimensions (nominal sizes in mm)
53,6
54
122,4
Width
Height
Depth
Note on dimensions
126,1
53.6 mm
126.1 mm
54 mm
The depth is valid when a TH 35-7.5 DIN rail is used (according to EN 60715).
General data
Color
Weight
traffic grey A RAL 7042
204 g (with connectors and bus base module)
7989_en_03
PHOENIX CONTACT
3
AXL F AI8 1F
General data
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
Degree of protection
Protection class
Mounting position
-25 °C ... 60 °C
-40 °C ... 85 °C
5 % ... 95 % (non-condensing)
5 % ... 95 % (non-condensing)
70 kPa ... 106 kPa (up to 3000 m above sea level)
70 kPa ... 106 kPa (up to 3000 m above sea level)
IP20
III, IEC 61140, EN 61140, VDE 0140-1
Any (no temperature derating)
Connection data
Designation
Connection method
Conductor cross section solid / stranded
Conductor cross section [AWG]
Stripping length
Axioline F connector
Push-in connection
0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
24 ... 16
8 mm
Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Interface Axioline F local bus
Connection method
Transmission speed
Bus base module
100 MBit/s
Communications power
Communications power U
Bus
Current consumption from U
Bus
Power consumption at U
Bus
5 V DC (via bus base module)
typ. 105 mA, max. 130 mA
typ. 0.525 W
I/O supply
Supply of analog modules U
A
Maximum permissible voltage range
Current consumption from U
A
Power consumption at U
A
Surge protection
Protection against polarity reversal
Transient protection
24 V DC
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
typ. 35 mA
max. 45 mA
typ. 0.84 W, max. 1.08 W
Electronic (35 V, 0.5 s)
Polarity protection diode
Suppressor diode
Total power consumption of the module
Power consumption
typ. 1.365 W (at U
Bus
and U
A
), max. 1.605 W (at U
Bus
and U
A
)
Analog inputs
Number of inputs
Connection method
Connection method
Current input signal
Voltage input signal
Resolution A/D
A/D conversion time
Limit frequency (3 dB)
max. 8 (Differential inputs, voltage or current can be chosen separately)
Push-in connection
2-wire (shielded, twisted pair)
0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA
0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V
16 bit
2 µs
30 Hz, 12 kHz (in fast mode)
7989_en_03
PHOENIX CONTACT
4
AXL F AI8 1F
Analog inputs
Measured value representation
Data formats
Process data update
Filtering
Input filter
Precision
Transient protection of inputs
16 bits (15 bits + sign bit)
IB IL, S7-compatible
300 µs
RFI filtering / passive TP 1st order
30 Hz, 12 kHz and mean-value generation (can be parameterized)
0.1 % (of measuring range final value for active mean-value generation and 30 Hz
filter)
Suppressor diode
differential inputs, voltage
Number of inputs
Voltage input signal
Input resistance of voltage input
Open circuit response
Common mode voltage range signal - ground
Overload protection
8
0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V
268 kΩ (typical)
Goes to 0 V
-50 V DC ... 50 V DC
±30 V DC, maximum
differential inputs, current
Number of inputs
Current input signal
Input resistance current input
Open circuit response
Overload protection
8
0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA
104
Ω
(typical)
Going to 0 mA; open-circuit detection from 4 mA ... 20 mA
No; ±5.2 V DC, maximum, I
max
= 50 mA
Configuration and parameter data in a PROFIBUS system
Required parameter data
Need for configuration data
27 Byte
6 Byte
Electrical isolation/isolation of the voltage areas
Test section
Logic
Analog I/O
Functional earth ground
Test voltage
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
Continuous shock according to EN 60068-2-27/IEC 60068-2-27
5g
30g
10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4
Transient surge voltage (surge) EN 61000-4-5/IEC 61000-4-5
Conducted interference EN 61000-4-6/IEC 61000-4-6
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022
Class B
Criterion B; 6 kV contact discharge, 8 kV air discharge
Criterion A; Field intensity: 10 V/m
Criterion B, 2 kV
Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); ±1 kV
to shielded I/O cables
Criterion A; Test voltage 10 V
7989_en_03
PHOENIX CONTACT
5