https://www.phoenixcontact.com/us/products/2805185
Type 2 surge protection plug - VAL-MS 1000PV ST - 2805185
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Replacement plug for PV arrester combinations of the VAL-MS 1000 DC... product range
Key commercial data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
80.0 GRM
85363010
Germany
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
52.4 mm
17.7 mm
54.5 mm
1 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
IP20
-40 °C ... 80 °C
General
Housing material
Inflammability class according to UL 94
Color
Standards for air and creepage distances
PA 6.6
V0
black
IEC 60664-1
IEC 61643-1
EN 61643-11
Mounting type
On base element
09/10/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2805185
Type 2 surge protection plug - VAL-MS 1000PV ST - 2805185
Technical data
General
Type
Number of positions
Surge protection fault message
Direction of action
Male
1
Optical
1L-N/PE
Protective circuit
IEC test classification
EN type
Nominal voltage U
N
Maximum continuous operating voltage U
C
U
T
(TOV-proof)
Nominal frequency f
N
Residual current I
PE
Standby power consumption P
C
Max. discharge current I
max
(8/20) µs
Nominal discharge current I
n
(8/20) µs
Impulse discharge current (10/350)½µs, peak value l
imp
Voltage protection level U
p
Residual voltage
II
T2
T2
400 V AC
580 V AC
690 V AC (5 s)
50 Hz (60 Hz)
≤ 250 µA
≤ 0.15 VA
30 kA
15 kA
1.25 kA
≤ 2.5 kV
≤ 2.5 kV
≤ 2.3 kV (at 10 kA)
≤ 2.1 kV (at 5 kA)
≤ 1.9 kV (at 3 kA)
Response time
Max. backup fuse with branch wiring
Short-circuit resistance I
P
with max. backup fuse (effective)
≤ 25 ns
125 A (gL / gG)
25 kA
Connection, protective circuit
Connection method
FLASHTRAB/VALVETRAB plug-in system connector
Standards and Regulations
Standards/regulations
IEC 61643-1 2005
DIN EN 61643-11 2002
Classifications
eCl@ss
eCl@ss 4.0
27140201
09/10/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2805185
Type 2 surge protection plug - VAL-MS 1000PV ST - 2805185
Classifications
eCl@ss
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27130801
27130801
27130801
27130805
27130805
27130805
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000941
EC000941
EC000941
EC000941
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Approvals
Approvals
Approvals
GOST / UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
GOST
09/10/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2805185
Type 2 surge protection plug - VAL-MS 1000PV ST - 2805185
Approvals
UL Recognized
cUL Recognized
cULus Recognized
Drawings
Dimensioned drawing
99
45
22,5
65,5
58
51,5
Phoenix Contact 2014 © - all rights reserved