75W Single Output Industrial DIN RAIL
NDR-75
series
Bauar t gepruft
Sicherheit
egel ma ge
od
o s
be wac
g
www.tuv.com
ID 2000000000
■
Features
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
/ Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
■
Applications
Industrial control system
Semiconductor fabrication equipment
Factory automation
Electro-mechanical apparatus
■
Description
NDR-75 is one economical slim 75W Din rail power supply series, adapt to be installed on TS-35/7.5
or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the
c a b i n e t s . T h e e n t i r e s e r i e s a d o p t s t h e f u l l r a n g e AC i n p u t fr o m 9 0 V A C to 2 6 4 V A C a n d c o n f o r m s to
EN61000-3-2, the norm the European Union regulates for harmonic current.
NDR-75 is designed with metal housing that enhances the unit's power dissipation. With working efficiency
up to 89%, the entire series can operate at the ambient temperature between -20
℃
and 70
℃
under air
convection. It is equipped with constant current mode for over-load protection, fitting various inductive
or capacitive applications. The complete protection functions and relevant certificates for industrial control
apparatus (UL508, TUV EN60950-1, and etc.) make NDR-75 a very competitive power supply solution for
industrial applications.
■
Model Encoding
NDR - 75 - 12
Output voltage
Output wattage
Series name
File Name:NDR-75-SPEC 2018-01-12
75W Single Output Industrial DIN RAIL
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
NDR-75-12
12V
6.3A
0 ~ 6.3A
75.6W
NDR-75-24
24V
3.2A
0 ~ 3.2A
76.8W
120mVp-p
24 ~ 28V
±1.0%
±0.5%
±1.0%
2000ms, 60ms/115VAC at full load
12ms/115VAC at full load
127 ~ 370VDC
NDR-75
NDR-75-48
48V
1.6A
0 ~ 1.6A
76.8W
150mVp-p
48 ~ 55V
±1.0%
±0.5%
±1.0%
series
RIPPLE & NOISE (max.)
Note.2
80mVp-p
VOLTAGE ADJ. RANGE
12 ~ 14V
VOLTAGE TOLERANCE
Note.3
±2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
Note.6
±0.5%
±1.0%
1200ms, 60ms/230VAC
60ms/230VAC
90 ~ 264VAC
47 ~ 63Hz
85.5%
1.45A/115VAC
20A/115VAC
<1mA / 240VAC
105 ~ 130% rated output power
0.9A/230VAC
35A/230VAC
[DC input operation possible by connecting AC/L(+), AC/N(-)]
88%
89%
INPUT
Protection type :
Constant current limiting, recovers automatically after fault condition is removed
14 ~ 17V
29 ~ 33V
56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
-20 ~ +70
℃
(Refer to "Derating Curve")
20 ~ 95% RH non-condensing
-40 ~ +85
℃
, 10 ~ 95% RH
±
0.03%/
℃
(0 ~ 50
℃
)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1,
EAC TP TC 004
approved;(meet EN60204-1)
I/P-O/P:3KVAC
I/P-FG:2KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25
℃
/ 70% RH
PROTECTION
OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
NOTE
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020
486.2K hrs min.
MIL-HDBK-217F (25
℃
)
32*125.2*102mm (W*H*D)
0.51Kg; 28pcs/15.3Kg/1.22CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25
℃
of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it
still meets EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with
full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
7. The ambient temperature derating of 3.5
℃
/1000m with fanless models and of 5
℃
/1000m with fan models for operating altitude higher than
2000m(6500ft).
File Name:NDR-75-SPEC 2018-01-12
75W Single Output Industrial DIN RAIL
Mechanical Specification
NDR-75
series
Case No.221B
Unit:mm
Top View
102
32
1234
39
TB2
(12V,24V only)
DC OK
+V ADJ.
125.2
(48V only)
TB1
123
Side View
Front View
Side View
Terminal Pin No. Assignment (TB1)
Pin No.
1
2
3
Assignment
FG
AC/N or DC -
AC/L or DC +
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
Bottom View
Assignment
DC OUTPUT -V
DC OUTPUT+V
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.
35
ADMISSIBLE DIN rail:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
Back View
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
File Name:NDR-75-SPEC 2018-01-12