TAC series(4-30A)
R
Three phase input type(1-stage filter)
Ordering information
TAC -10 -683
1
2
3
4
-O
1
Model Name
2
Rated Current
3
Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code
103
223
683
Line to ground
Leakage Current
capacitor
(Input 250/500V 60Hz)
(nominal value)
0.5mA/1.0mA max
10000pF
1.0mA/2.0mA max
22000pF
2.5mA/5.0mA max
68000pF
4
Options
D :DIN rail installation type
*
The dimensions change when the option is set.
Refer to External view.
The terminal cover is retracted inside the unit
DIN rail installation type is option
Features of TAC series
High-attenuation type of common mode noise from 150kHz to 1MHz (1-stage filter)
-
Three phase rated voltage 500 VAC (voltage range:528V max)
-
Selectable leakage current value
-
Push down type terminal block
Specifications
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Items
Rated Voltage[V]
Rated Current[A]
Test Voltage (Terminal-Mounting Plate)
Isolation Resistance (Terminal-Mounting Plate)
Leakage current 250/500V 60Hz
Voltage drop
Safety agency approval temperatures
Operating temperature
Operating humidity
Storage temperature/humidity
Vibration
Impact
Safety agency approvals
Case size (without projection) /Weight
TAC-04-683
4
TAC-06-683
6
TAC-10-683
10
TAC-20-683
20
TAC-30-683
30
AC Three Phase 500 (voltage range:528 max) 50/60Hz
2,000 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity
500 VDC 100MW min at room temperature and humidity
2.5mA/5.0mA max
1.5V max
-25 to +85C (Refer to Derating Curve)
-40 to +85C (Refer to Derating Curve)
20 to 95%RH (Non condensing)
-40 to +85C/20 to 95%RH (Non condensing)
10 to 55Hz, 19.6m/s
2
(2G), 3min. Period, 1hour each X, Y and Z axis
196.1m/s
2
(20G), 11ms Once each X, Y and Z axis
UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
63X64X128 mm [2.48X2.52X5.04 inches] (WXHXD) /620g max (Option : -D refer to external view)
1.0V max
Circuit Diagram
Case
LINE
1
2
3
LOAD
4
5
6
Derating Curve
100
Load Factor [%]
80
60
40
20
0
-40
-30
-20
40
50
60
70
80
90
CY
CY
CY : Line to ground capacitor
: Mounting Plate
Ambient Temperature [C]
TA-1
TAC,TAH series(4-30A)
External view
As this product is adopted push-down type terminal block, this appearance is as follows.
1The
terminal cover is retracted inside the unit.
2The
screws for connecting the terminals are held in the up right position.
Standard Type
[5.04]
128
Mounting Plate
Protection Earth
Input
Terminal
118
±
0.5
[4.65]
(2.5)
[0.1]
[1.97]
50
[3.29]
83.5
[0.79]
20
[0.75]
19
Output
Terminal
[0.47]
Output
Terminal
Terminal cover
¶
Closed the terminal cover
7-M4
Terminal cover
[0.22]
Mounting Hole
[0.08]
4-f5.5
(2)
¶
Tolerance :
±1
[±0.04]
¶
Weight : 620g max
¶
Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 [0.04]
¶
Case : PBT
¶
Dimensions in mm, [ ]=inches
¶
Terminal block screw tighting torque M4:1.6N-m (16.9kgf-cm) max
DIN rail installation Type
Input
Terminal
[4.25]
[3.29]
108
83.5
[0.39] [0.43]
10 (11)
[2.52]
64
Mounting Plate
Protection Earth
Output
Terminal
Output
Terminal
Output
Terminal
[0.47]
[2.48]
[2.48]
Input
Terminal
63
Output
Terminal
[1.97]
12
Name Plate
50
±
0.5
(2.5)
[0.1]
[1.97]
50
[0.79]
20
[0.75]
19
Input
Terminal
Terminal cover
¶
Closed the terminal cover
7-M4
Terminal cover
[0.08]
(2)
[2.52]
64
12
(9)
[0.35]
DIN rail
¡
Note when installing the EMI/EMC
Filter on a DIN rail.
When the EMI/EMC Filter is grounded through
the DIN rail, the proper noise attenuation may not
be achieved.
Be sure to connect the protection earth (PE) of
the EMI/EMC Filter body to the earth.
Name Plate
[0.28]
7
63
Name Plate
¶
Tolerance :
±1
[±0.04]
¶
Weight : 620g max
¶
Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 [0.04]
¶
Case : PBT
¶
Dimensions in mm, [ ]=inches
¶
Terminal block screw tighting torque M4:1.6N-m (16.9kgf-cm) max
DIN rail
TA-3