https://www.phoenixcontact.com/us/products/1573374
Sensor/Actuator cable - SAC-4P-MR/ 5,0-PVC SCO - 1573374
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Sensor/Actuator cable, 4-position, PVC, black RAL 9005, Plug angled M12 SPEEDCON, A-coded, on free cable
end, Cable length: 5 m
Key Commercial Data
Packing unit
Minimum order quantity
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
25 pc
222.22 g
85444290
Poland
Technical data
Dimensions
Length of cable
Stripping length of the free conductor end
5m
50 mm
Ambient conditions
Degree of protection
IP65
IP67
IP68
General
Rated current at 40°C
Rated voltage
Number of positions
Insulation resistance
Coding
Status display
4A
250 V
4
≥ 10 MΩ
A - standard
No
04/25/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/1573374
Sensor/Actuator cable - SAC-4P-MR/ 5,0-PVC SCO - 1573374
Technical data
General
Overvoltage category
Degree of pollution
II
3
Material
Flammability rating according to UL 94
Contact material
Contact surface material
Contact carrier material
Material of grip body
Material, knurls
HB
CuSn
Ni/Au
TPU GF
TPU, hardly inflammable, self-extinguishing
Zinc die-cast, nickel-plated
Standards and Regulations
Flammability rating according to UL 94
HB
Cable
Cable type
Cable type (abbreviation)
Cable abbreviation
UL AWM style
Conductor cross section
AWG signal line
Conductor structure signal line
Core diameter including insulation
Thickness, insulation
Wire colors
Overall twist
External sheath, color
Outer sheath thickness
External cable diameter D
Minimum bending radius, fixed installation
Minimum bending radius, flexible installation
Cable weight
Outer sheath, material
Material conductor insulation
Conductor material
Insulation resistance
Conductor resistance
Nominal voltage, cable
Test voltage, cable
PVC black
PVC
LiYY
2464 / 1729 (80°C/300 V)
4x 0.34 mm² (Signal line)
22
42x 0.10 mm
1.45 mm ±0.02 mm
≥ 0.23 mm (Core insulation)
brown, white, blue, black
4 wires, twisted
black RAL 9005
≥ 0.76 mm
5.2 mm ±0.15 mm
5xD
10 x D
40 kg/km
PVC
PVC
Bare Cu litz wires
≥ 200 MΩ*km (at 20 °C)
max. 58 Ω/km (at 20 °C)
≤ 300 V
≥ 3000 V
04/25/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/1573374
Sensor/Actuator cable - SAC-4P-MR/ 5,0-PVC SCO - 1573374
Technical data
Cable
Flame resistance
According to UL 758/1581 FT1
According to UL 758/1581 (Cable Flame)
According to DIN EN 60332-1-2
Resistance to oil
Ambient temperature (operation)
according to DIN EN 60811-2-1, 168 h at 60 °C
-40 °C ... 80 °C (cable, fixed installation)
-25 °C ... 80 °C (cable, flexible installation)
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27060306
27060306
27061801
27061801
27061801
27061801
27279218
ETIM
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001855
EC001855
EC001855
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
31251501
31251501
31251501
31251501
31251501
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
04/25/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/1573374
Sensor/Actuator cable - SAC-4P-MR/ 5,0-PVC SCO - 1573374
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Listed
Nominal current IN
Nominal voltage UN
4A
300 V
cUL Listed
Nominal current IN
Nominal voltage UN
4A
300 V
cULus Listed
Drawings
Schematic diagram
4
3
Cable cross section
1
2
Pin assignment M12 plug, 4-pos., A-coded, view plug side
PVC black [PVC]
04/25/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/1573374
Sensor/Actuator cable - SAC-4P-MR/ 5,0-PVC SCO - 1573374
Dimensional drawing
Ø14,8
M12
1
2
BN
WH
BK
BU
Circuit diagram
30,2
4
3
34,5
Ø11
Contact assignment of the M12 plugs
M12 x 1 male plug, angled
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com