Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
8719NH Multi-Conductor - GreenChoice Multiconductor
For more Information
please call
1-800-Belden1
General Description:
16 AWG stranded (19x29) TC conductors, polyethylene insulation, twisted pair, overall Beldfoil® shield
(100% coverage), 18 AWG stranded TC drain wire, LSZH jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
1
16
19x29
TC - Tinned Copper
2
Total Number of Conductors:
Insulation
Insulation Material:
Insulation Material Wall Thickness (in.)
PE - Polyethylene
0.028
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material
Beldfoil®
Coverage (%)
Tape Aluminum Foil-Polyester Tape w/Shorting Fold 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
18
Stranded
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
LSZH- Low Smoke Zero Halogen 0.032
Overall Cable
Overall Nominal Diameter:
0.300 in.
Pair
Pair Color Code Chart:
Number Color
1
Black & Clear
Pair Lay Length & Direction:
Lay Length (in.) Twists (twist/ft)
2.750
4.400
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-20°C To +80°C
80°C
44 lbs/1000 ft.
102 lbs.
3 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
CMG
CMG
Yes
Yes
Yes
Yes
Page 1 of 2
08-26-2016
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
8719NH Multi-Conductor - GreenChoice Multiconductor
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Other Specification:
05/07/2012
Yes
Yes
Yes
Yes
UL AWM 21310
Flame Test
UL Flame Test:
C(UL) Flame Test:
UL1685 FT4 Loading
FT4
Suitability
Suitability - Indoor:
Non-halogenated:
Yes
Yes
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/ft)
.2
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
26.000
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/ft)
46.750
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
4.5
Max. Operating Voltage - UL:
Voltage
Description
600 V RMS UL AWM 21310
300 V RMS UL type CMG
Max. Recommended Current:
Current
7 Amps per conductor @ 25°C
Put Ups and Colors:
Item #
8719NH 0601000
8719NH 060500
Putup
1,000 FT
500 FT
Ship Weight
48.000 LB
25.500 LB
Color
CHROME
CHROME
Notes
Item Desc
2 #16 LDPO FS NHFRPO
3 #18 LDPE FS NHFRPO
Revision Number: 0
© 2016 Belden, Inc
All Rights Reserved.
Revision Date: 08-16-2016
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 2 of 2
08-26-2016