IB IL 120 DI 1
INTERBUS Inline Terminal With One Digital
Input in the 120 V AC Voltage Area
Data Sheet 5764B
5 7 6 4 1 0 0 1
09/2000
This data sheet is only valid in
association with the INTERBUS
Inline System Manual
IB IL SYS PRO UM E.
Function
The terminal is designed for use within an
INTERBUS Inline station. This terminal is used
to detect digital input signals in the 120 V AC
voltage area.
Dangerous Voltage
Connecting and disconnecting the
terminal is only allowed if the
power
supply is disconnected.
When working on the terminal and
wiring, always switch off the supply
voltage and ensure it cannot be
switched on again.
If these instructions are not
followed, there is a danger of
damage to health, or even of a
life-threatening injury.
Features
–
–
–
Connections for one digital sensor
Maximum permissible load current 500 mA
Diagnostic and status indicators
5 7 6 4 1 0 0 7
Figure 1
IB IL 120 DI 1 terminal
with connector
Please note that the connector is not
supplied with the terminal. Please
refer to Ordering Data on page 12 to
order the appropriate connectors for
your application.
5764B
1
IB IL 120 DI 1
Safety Instructions for Inline Terminals for Installation in
Areas Outside the SELV (Low Voltage Area)
Only qualified personnel may work on low voltage area Inline terminals.
Qualified personnel are people who, because of their education, experience and instruction, and their
knowledge of relevant standards, regulations, accident prevention and service conditions, have been
authorized by those responsible for the safety of the plant to carry out any required operations, and
who are able to recognize and avoid any possible dangers.
(Definitions for skilled workers according to EN 50110-1:1996.)
The instructions given in this data sheet must be followed during installation and startup.
Technical modifications reserved.
Correct Usage
The terminal is only to be used within an Inline station as specified in this data sheet and the
INTERBUS Inline System Manual. Phoenix Contact accepts no liability if the device is used for
anything other than its designated use.
This data sheet describes the module-specific features of the IB IL 120 DI 1 terminal.
For general information on the INTERBUS Inline product family, please refer to the
IB IL SYS PRO UM E INTERBUS Inline System Manual.
2
5764B
IB IL 120 DI 1
General Description
Local Diagnostic and Status Indicators
1
D
Des.
D
1
Color Meaning
Green Bus diagnostics
Yellow Input status indication
1 2 0 D I1
Terminal Assignment
Terminal Assignment
Point
1.1
1.2
1.3
1
2
Not used
Digital input
Connection of phase L
Neutral conductor connection (N)
Not used
1.4
1
1 .1
1
2 .1
2
2.1, 2.2,
2.3, 2.4
1 .2
2
2 .2
3
1 .3
3
2 .3
4
1 .4
4
2 .4
5 7 6 4 1 0 0 2
Figure 2
IB IL 120 DI 1
with the appropriate connector
Function Identification
Cobalt blue with lightning bolt
Housing/Connector Color
Gray housing
Gray connector, color-coded according to
function
5764B
3
IB IL 120 DI 1
Internal Circuit Diagram
Key:
IN T E R B U S
O P C
OPC
U
L
INTERBUS protocol chip
(bus logic including voltage
conditioning)
LED
Optocoupler
Digital input
Isolated area
Terminal point, without metal
contact
Terminal point, without metal
contact, with filler plugs
L (1 2 0 V A C )
N
Other symbols are explained in the
IB IL SYS PRO UM E User Manual.
5 7 6 4 B 0 0 3
Figure 3
Internal wiring of the terminal points
4
5764B
IB IL 120 DI 1
General Installation Instructions
Installing the System
Install the system according to the
requirements of EN 50178.
Starting Up an Inline Station
An Inline station can only be started up if it has
been properly installed. This means:
–
–
all terminals must be installed with their
connectors
the station must be terminated with the end
plate and the two end clamps
Avoiding malfunctions
The AC terminal must
only
be
connected to the Inline station
through an appropriate power
terminal. The voltage should only be
switched on when the AC area has
been terminated with the end terminal
and all the connectors are connected.
The special features of the AC and
SELV terminals and connectors
are listed in the user manual and in
the data sheets for the power
terminals for AC areas.