https://www.phoenixcontact.com/hq/products/2905882
Current transformer - PACT MCR-V2-4012-70-250-1A-1 - 2905882
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Window-type current transformer, 250 A AC primary current; 1 A AC secondary current; accuracy class 1; 5
VA rated power
Key Commercial Data
Packing unit
GTIN
GTIN
Custom tariff number
Note
4055626004822
85043129
Made to Order (non-returnable)
1 STK
Technical data
Dimensions
Primary round conductor (diameter)
Primary round conductor (width)
Primary round conductor (height)
Note on dimensions
Primary round conductor (width)
Primary round conductor (height)
Width
Height
Depth
Width with alternative assembly
Height with alternative assembly
Depth with alternative assembly
33 mm
40 mm
12 mm
2
30 mm
10 mm
30 mm
90 mm
70 mm
70 mm
90 mm
30 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-25 °C ... 40 °C
-25 °C ... 40 °C
11/15/2016 Page 1 / 2
https://www.phoenixcontact.com/hq/products/2905882
Current transformer - PACT MCR-V2-4012-70-250-1A-1 - 2905882
Technical data
Input data
Thermal rated short-time current
Thermal rated continuous current
Rated surge current
Rated frequency: Standard converter
Rated frequency: Calibrated converter
Surge current limitation factor
Rated power
Primary rated current I
pn
Secondary rated current I
sn
I
th
= 60 * I
n
I
d
= 1.2 * I
n
I
dyn
= 2.5 * I
th
50 Hz ... 60 Hz
50 Hz
FS 5
5 VA
0 A ... 250 A
1 A AC
General
Converter type
Accuracy class
Can be calibrated
Rated insulation voltage
Standards/regulations
Housing material
Plug-on converters
1
no
1 kV (Phase/neutral conductor)
EN 50178
EN 61869
WELLAMID 6600-PA66-GV 20 HWV0CP
Standards and Regulations
Standards/regulations
EN 50178
EN 61869
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Dimensional drawing
70
30
16
40,5x13
31x31
13x40,5
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
11/15/2016 Page 2 / 2
74
33