Product data sheet
Characteristics
8501XO20XTD1V02
Timing Relay - One Minute Off-Delay with
120VAC Coil with 2 NO Contacts
Product availability : Non-Stock - Not normally stocked in distribution facility
Price* : 480.00 USD
Main
Range of product
Relay type
Product or component type
[In] rated current
Poles description
Maximum switching voltage
8501X
Timing
Relay
10 A AC
5 A DC
2P
600 V AC
Complementary
[Uc] control circuit voltage
Control circuit voltage limits
Rated breaking capacity
110 V AC 50 Hz
120 V AC 60 Hz
0.85...1.1 Uc operational AC 50/60 Hz
6 A at: 120 V AC for inductive load control circuit per UL 508
3 A at: 240 V AC for inductive load control circuit per UL 508
1.5 A at: 480 V AC for inductive load control circuit per UL 508
1.2 A at: 600 V AC for inductive load control circuit per UL 508
10 A at: <= 600 V AC for resistive load control circuit per UL 508
1.1 A at: 125 V DC for inductive load control circuit per UL 508
0.55 A at: 250 V DC for inductive load control circuit per UL 508
0.2 A at: 301...600 V DC for inductive load control circuit per UL 508
4 A at: 125 V DC for resistive load control circuit per UL 508
0.8 A at: 250 V DC for resistive load control circuit per UL 508
60 A at: 120 V AC for inductive load control circuit per UL 508
30 A at: 240 V AC for inductive load control circuit per UL 508
15 A at: 480 V AC for inductive load control circuit per UL 508
12 A at: 600 V AC for inductive load control circuit per UL 508
10 A at: <= 600 V AC for resistive load control circuit per UL 508
1.1 A at: 125 V DC for inductive load control circuit per UL 508
0.55 A at: 250 V DC for inductive load control circuit per UL 508
0.2 A at: 301...600 V DC for inductive load control circuit per UL 508
4 A at: 125 V DC for inductive load control circuit per UL 508
0.8 A at: 250 V DC for resistive load control circuit per UL 508
1
[Icm] rated short-circuit making
capacity
Dec 19, 2018
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Time delay type
Time delay range
Inrush power in VA
Hold-in power consumption in VA
Operating time
Contacts type and composition
Electrical connection
AWG gauge
Tightening torque
Mounting support
Ambient air temperature for operation
Height
Width
Depth
Off-delay
0.2...60 s
148 VA at 60 Hz
143 VA at 50 Hz
At 60 Hz
At 50 Hz
15 ms pick-up
16 ms drop-out
2 NO 2 standard contact cartridges
Screw clamp terminals
AWG 18...AWG 12 copper
1.02...1.36 N.m control circuit screw terminal
Panel
-40...160 °F
3.5 in
2.23 in
6.55 in
Environment
Product certifications
UL listed file E78403 CCN NKCR
CSA LR60905 class 3211 03
Ordering and shipping details
Category
Discount Schedule
GTIN
Nbr. of units in pkg.
Package weight(Lbs)
Returnability
Country of origin
21158 - 8501 XO (AC)
CP2
00785901537403
1
2.5899999999999999
Y
MX
Offer Sustainability
Sustainable offer status
RoHS (date code: YYWW)
REACh
Product environmental profile
Product end of life instructions
California proposition 65
- - - - - - - Substance 1
- - - - - - - More information
Green Premium product
Compliant - since 1332 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Available
Available
WARNING: This product can expose you to chemicals including:
Lead and lead compounds, which is known to the State of California to cause cancer and birth
defects or other reproductive harm.
For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period
18 months
2