https://www.phoenixcontact.com/us/products/2805457
Type 2 surge protection device - VAL-MS 600DC/2+V - 2805457
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge arrester for 2-pos. isolated and grounded DC voltage systems 600 V DC, for DIN rail mounting, 3-pos.
base element (L+, L-, ground), three pluggable temperature-monitored varistors, status message on each
connector.
Product Features
Plugs can be checked with CHECKMASTER
With or without floating remote indication contact
Optical, mechanical status indication for the individual arresters
Type 2 consistent plug-in surge arresters
Mechanical coding of all slots
Packing unit
1 pc
320.0 GRM
85363010
Germany
Key commercial data
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
90 mm
53.4 mm
65.5 mm
3 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
IP20
-40 °C ... 80 °C
09/10/2014 Page 1 / 5
https://www.phoenixcontact.com/us/products/2805457
Type 2 surge protection device - VAL-MS 600DC/2+V - 2805457
Technical data
General
Housing material
Inflammability class according to UL 94
Color
Standards for air and creepage distances
Mounting type
Type
Number of positions
Surge protection fault message
Direction of action
PBT / PA
V0
black
DIN EN 60664-1
DIN EN 61643-11
DIN rail: 35 mm
DIN rail module, two-section, divisible
3
Optical
(L+)-PE & (L-)-PE & (L+)-(L-)
Protective circuit
IEC test classification
EN type
Nominal voltage U
N
Maximum continuous operating voltage U
C
Rated load current I
L
Residual current I
PE
Standby power consumption P
C
Max. discharge current I
max
(8/20) µs
Nominal discharge current I
n
(8/20) µs
Voltage protection level U
p
Voltage protection level U
p
(L+) - (L-)
Voltage protection level U
p
(L+/L-) - PE
Residual voltage (L+) - (L-)
Residual voltage (L+/L-) - PE
Response time
II
T2
T2
600 V DC (Non-load voltage U
OC
)
600 V DC
≤ 80 A DC
≤ 20 µA
≤ 12 mW
40 kA
15 kA
≤ 3 kV (15 kA)
≤ 3.6 kV (20 kA)
≤ 3 kV
≤ 3 kV
≤ 2.5 kV (at 5 kA)
≤ 2.5 kV (at 5 kA)
≤ 2.5 kV (at 5 kA)
≤ 25 ns
PV protective circuit DC side
Short-circuit current rating I
SCPV
80 A
Connection, protective circuit
Connection method
Connection type IN
Connection type OUT
Screw connection
Biconnect screw terminal block
Biconnect screw terminal block
09/10/2014 Page 2 / 5
https://www.phoenixcontact.com/us/products/2805457
Type 2 surge protection device - VAL-MS 600DC/2+V - 2805457
Technical data
Connection, protective circuit
Connection method
Screw thread
Tightening torque
Stripping length
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
AWG conductor cross section
Biconnect terminal block
M5
4.5 Nm
30 lb
f
-in. (UL)
16 mm
1.5 mm²
25 mm²
1.5 mm²
35 mm²
15
2
10 ... 2 (UL)
Standards and Regulations
Standards/regulations
DIN EN 61643-11/A11 2007
IEC 61643-1 2005
IEC 60364-7-712 2002
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27140201
27130801
27130801
27130801
27130805
27130805
27130805
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000941
EC000941
EC000942
EC000942
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
30212010
39121610
09/10/2014 Page 3 / 5
https://www.phoenixcontact.com/us/products/2805457
Type 2 surge protection device - VAL-MS 600DC/2+V - 2805457
Classifications
UNSPSC
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
39121610
39121610
39121620
Approvals
Approvals
Approvals
GOST / UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
GOST
UL Recognized
cUL Recognized
cULus Recognized
Drawings
09/10/2014 Page 4 / 5
https://www.phoenixcontact.com/us/products/2805457
Type 2 surge protection device - VAL-MS 600DC/2+V - 2805457
Dimensioned drawing
99
45
22,5
Circuit diagram
65,5
58
L+
L–
The illustration shows the dimensional drawing for a version with remote
indicator contact
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
51,5