https://www.phoenixcontact.com/hq/products/2906451
Type 3 surge protection plug - PLT-T3-IT-230-P - 2906451
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Replacement plug for device protection in IT systems from the PLUGTRAB product series. 230 V nominal
voltage.
Key Commercial Data
Packing unit
GTIN
GTIN
Custom tariff number
4055626077345
85363010
1 STK
Technical data
Dimensions
Height
Width
Depth
45 mm
17.7 mm
52 mm
Ambient conditions
Degree of protection
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
IP20
-40 °C ... 70 °C
-40 °C ... 70 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
General
IEC test classification
EN type
Number of ports
SPD design
Mode of protection
III
T3
T3
One
Combination type
L-L
11/15/2016 Page 1 / 3
https://www.phoenixcontact.com/hq/products/2906451
Type 3 surge protection plug - PLT-T3-IT-230-P - 2906451
Technical data
General
L-PE
Mounting type
Color
Housing material
Degree of pollution
Flammability rating according to UL 94
On base element
jet black RAL 9005
PA 6.6
2
V-0
Protective circuit
Nominal voltage U
N
Nominal frequency f
N
Maximum continuous operating voltage U
C
(L-N)
Maximum continuous operating voltage U
C
(L-PE)
Rated load current I
L
Residual current I
PE
Nominal discharge current I
n
(8/20) µs
Standby power consumption P
C
Reference test voltage U
REF
Max. discharge current I
max
(8/20) µs
Combination wave U
OC
Voltage protection level U
p
(L-N)
Voltage protection level U
p
(L-PE)
TOV behavior at U
T
(L-PE)
Response time t
A
(L-N)
Response time t
A
(L-PE)
Max. required back-up fuse
Short-circuit current rating I
SCCR
Max. backup fuse with branch wiring
Maximum backup fuse for through wiring
230 V AC (IT)
50 Hz (60 Hz)
275 V AC
440 V AC
16 A (60°C)
≤ 1 µA
3 kA
≤ 340 mVA
255 V AC
8 kA
6 kV
≤ 1.2 kV
≤ 1.5 kV
440 V AC (120 min / withstand mode)
1455 V AC (200 ms / safe failure mode)
≤ 25 ns
≤ 100 ns
16 A (MCB-B)
1.5 kA AC
16 A (MCB-B)
16 A (MCB-B)
Connection data
Connection method
pluggable
Standards and Regulations
Standards/specifications
IEC 61643-11 2011
EN 61643-11 2012
Drawings
11/15/2016 Page 2 / 3
https://www.phoenixcontact.com/hq/products/2906451
Type 3 surge protection plug - PLT-T3-IT-230-P - 2906451
Circuit diagram
L
Dimensional drawing
90
44,8
L
PE
65,5
The figure shows the complete module consisting of a base element and connector
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
51,5
11/15/2016 Page 3 / 3