Type 1 / Class I / B arrester (lightning current arrester) with encapsulated arc chopping spark gap, 3-channel.
Housing width: 52.5 mm (3 Div.)
The illustration shows version FLT
35/3 CTRL-0.9/I
Key commercial data
Packing unit
Custom tariff number
Country of origin
1 pc
85363010
Germany
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
94 mm
53 mm
65.7 mm
3 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
Permissible humidity (operation)
IP20
-40 °C ... 85 °C
≤ 95 %
General
IEC power supply system
Housing material
Inflammability class according to UL 94
Color
Standards for air and creepage distances
TT
TN-C
PA-GF
V0
black
EN 60664-1
09/10/2014 Page 1 / 5
https://www.phoenixcontact.com/us/products/2800129
Lightning arrester type 1 - FLT 35/3 - 2800129
Technical data
General
EN61643-11
Mounting type
Type
Number of positions
Surge protection fault message
Direction of action
DIN rail: 35 mm
Rail-mountable module, one-piece
3
None
3L-PEN
Protective circuit
IEC test classification
EN type
Nominal voltage U
N
Maximum continuous operating voltage U
C
Maximum continuous operating voltage U
C
(L-PEN)
U
T
(TOV-proof)
Nominal frequency f
N
Residual current I
PE
Standby power consumption P
C
Max. discharge current I
max
(8/20) µs
Nominal discharge current I
n
(8/20) µs
Impulse discharge current (10/350) µs charge
Impulse discharge current (10/350)½µs, specific energy
Impulse discharge current (10/350)½µs, peak value l
imp
Impulse discharge current (10/350) µs charge
Impulse discharge current (10/350)½µs, specific energy
Impulse discharge current (10/350)½µs, peak value l
imp
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-N)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PEN)
Voltage protection level U
p
(L-N)
Voltage protection level U
p
(L-PEN)
Response time
Max. backup fuse with branch wiring
Short-circuit resistance I
P
with max. backup fuse (effective)
Follow current quenching capacity If (L-N)
I
T1
T1
230 V AC (400 V AC)
350 V AC
350 V AC
350 V (5 sec.)
50 Hz
60 Hz
≤ 0.3 mA
≤ 105 mVA
35 kA
100 kA (all channels)
35 kA
100 kA (all channels)
17.5 As
306 kJ/Ω
35 kA
50 As
2500 kJ/Ω
100 kA (all channels)
≤ 5 kV
≤ 5 kV
≤ 5 kV
≤ 5 kV
≤ 100 ns
400 A (gL)
25 kA
1.5 kA (350 V AC)
09/10/2014 Page 2 / 5
https://www.phoenixcontact.com/us/products/2800129
Lightning arrester type 1 - FLT 35/3 - 2800129
Technical data
Protective circuit
Follow current quenching capacity If (L-PEN)
3 kA (260 V AC)
Connection, protective circuit
Connection method
Connection type IN
Connection type OUT
Connection method
Screw thread
Tightening torque
Stripping length
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Screw connection
Biconnect screw terminal block
Biconnect screw terminal block
Biconnect terminal block
M5
4.5 Nm
14.5 mm
0.5 mm²
25 mm²
0.5 mm²
35 mm²
20
2
Standards and Regulations
Standards/regulations
IEC 61643-1 2005
DIN EN 61643-11 2002
DIN EN 61643-11/A11 2007
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27140201
27140201
27140201
27140201
27140201
27140201
27140201
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000381
EC000381
EC000381
EC000381
09/10/2014 Page 3 / 5
https://www.phoenixcontact.com/us/products/2800129
Lightning arrester type 1 - FLT 35/3 - 2800129
Classifications
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Approvals
Approvals
Approvals
KEMA-KEUR / GOST
Ex Approvals
Approvals submitted
Approval details
KEMA-KEUR
GOST
Drawings
09/10/2014 Page 4 / 5
https://www.phoenixcontact.com/us/products/2800129
Lightning arrester type 1 - FLT 35/3 - 2800129
Dimensioned drawing
90
45
Circuit diagram
L1
L2
L3
65,5
58
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
51,5
PEN /
09/10/2014 Page 5 / 5