https://www.phoenixcontact.com/hq/products/2907263
Type 1 surge protection plug - FLT-SEC-P-T1-N/PE-440/100-P - 2907263
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Replacement plug for lightning current arresters from the FLASHTRAB SEC product range, for the N-PE path.
Why buy this product
Spark gap has no line follow current
Free of leakage current
High continuous voltage of 440 V AC for 400/690 V AC networks with high voltage fluctuations
Satisfies TOV requirements for use in IT systems
Pluggable
Low voltage protection level of 2.5 kV
Optical, mechanical status indicator
Plugs can be checked with CHECKMASTER 2
Key Commercial Data
Packing unit
GTIN
GTIN
Custom tariff number
Note
4055626176727
85363010
Made to Order (non-returnable)
1 STK
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
46.4 mm
35.5 mm
59.4 mm
2 Div.
Ambient conditions
11/15/2016 Page 1 / 3
https://www.phoenixcontact.com/hq/products/2907263
Type 1 surge protection plug - FLT-SEC-P-T1-N/PE-440/100-P - 2907263
Technical data
Ambient conditions
Degree of protection
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
Shock (operation)
Vibration (operation)
IP20
-40 °C ... 80 °C
-40 °C ... 80 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
5g (5 - 500 Hz/2.5 h/X, Y, Z)
General
IEC test classification
EN type
IEC power supply system
SPD design
Mode of protection
Mounting type
Color
Housing material
Degree of pollution
Flammability rating according to UL 94
Design
Number of positions
Surge protection fault message
I / II
T1 / T2
T1 / T2
TT
Voltage-switching type
N-PE
On base element
light grey RAL 7035
PA 6.6-FR 20% GF
PBT-FR
2
V-0
Male
1
optical
Protective circuit
Nominal voltage U
N
Nominal frequency f
N
Maximum continuous voltage U
C
Residual current I
PE
Nominal discharge current I
n
(8/20) µs
Impulse discharge current (10/350)½µs, charge
Impulse discharge current (10/350)½µs, specific energy
Impulse discharge current (10/350)½µs, peak value l
imp
Follow current interrupt rating I
fi
Voltage protection level U
p
Residual voltage U
res
Front of wave sparkover voltage at 6 kV (1.2/50) µs
TOV behavior at U
T
Response time t
A
400 V AC (TN - only N-PE)
400 V AC (TT - only N-PE)
50 Hz (60 Hz)
440 V AC
≤ 0.01 mA
100 kA
50 As
2500 kJ/Ω
100 kA
100 A (440 V AC)
≤ 2.5 kV
≤ 2.5 kV (at I
n
)
≤ 2.5 kV
1200 V AC (200 ms / withstand mode)
≤ 100 ns
11/15/2016 Page 2 / 3
https://www.phoenixcontact.com/hq/products/2907263
Type 1 surge protection plug - FLT-SEC-P-T1-N/PE-440/100-P - 2907263
Technical data
Standards and Regulations
Standards/regulations
IEC 61643-11 2011
EN 61643-11 2012
Drawings
Circuit diagram
Dimensional drawing
46,4
35,5
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
59,4
52,3
11/15/2016 Page 3 / 3