https://www.phoenixcontact.com/pi/products/2702006
Communication module - AXL F RS UNI XC 1H - 2702006
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Axioline F communication module, extreme conditions version, for serial data transmission, 1 interface can be
parameterized as RS‑485/RS-422 or RS‑232 (including bus base module and plugs)
The figure shows the standard item
Product Description
The module is designed for use within an Axioline F station.
The module is used to operate standard I/O devices with serial interfaces on a bus system.
Thanks to special engineering measures and tests, the module can be used under extreme ambient conditions.
Your advantages
A serial input and output channel in RS-232, RS-422, and RS-485 format
Various protocols supported
Transmission speed can be set up to 250,000 baud
Parameterization via the PDI channel
Device rating plate stored
Can be used under extreme ambient conditions
Extended temperature range of -40°C ... +70°C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
Partially coated PCBs
Key Commercial Data
Packing unit
GTIN
GTIN
4046356909587
1 pc
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
35 mm
10/27/2018 Page 1 / 5
https://www.phoenixcontact.com/pi/products/2702006
Communication module - AXL F RS UNI XC 1H - 2702006
Technical data
Dimensions
Height
Depth
Note on dimensions
126.1 mm
54 mm
The depth is valid when a TH 35-7,5 DIN rail is used (according to
EN 60715).
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under
extreme ambient conditions” in the data sheet.)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
Degree of protection
-40 °C ... 85 °C
5 % ... 95 % (non-condensing)
5 % ... 95 % (non-condensing)
70 kPa ... 106 kPa (up to 3000 m above sea level)
70 kPa ... 106 kPa (up to 3000 m above sea level)
IP20
Connection data
Designation
Connection method
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Stripping length
Axioline F connector
Push-in connection
0.2 mm²
1.5 mm²
0.2 mm²
1.5 mm²
24
16
8 mm
General
Mounting type
Net weight
Note on weight specifications
Diagnostics messages
DIN rail
187.4 g
with connectors and bus base module
I/O supply failure Yes
Interfaces
Designation
No. of channels
Connection method
Transmission speed
Interface
Connection method
Transmission physics
Protocols supported
Termination resistor
Data bits
Axioline F local bus
2
Bus base module
100 Mbps
RS-232, RS-485, RS-422
Push-in connection
Copper
Transparent, end-to-end, XON/XOFF, Modbus/RTU (master support)
active, integrated
5 ... 8
10/27/2018 Page 2 / 5
https://www.phoenixcontact.com/pi/products/2702006
Communication module - AXL F RS UNI XC 1H - 2702006
Technical data
Interfaces
Stop bits
Input buffer
Output buffer
1 or 2
4 kByte
1 kByte
Axioline potentials
Designation
Supply voltage
Current consumption
Axioline F local bus supply (U
Bus
)
5 V DC (via bus base module)
typ. 200 mA
max. 240 mA
Serial input/output channel
Parity
Transmission type
Even, odd or no parity
Transparent mode, end-to-end mode, XON/XOFF, Modbus/RTU
Electrical isolation
Test section
5 V supply (logic)/5 V supply (I/O) 500 V AC 50 Hz 1 min.
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min.
5 V supply (I/O)/functional earth ground 500 V AC 50 Hz 1 min.
Standards and Regulations
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
Connection diagram
35
00
01
02
03
00
01
02
03
10
11
12
13
10
11
12
13
Dimensional drawing
54
20
21
22
23
20
21
22
23
30
31
32
33
30
31
32
33
122,4
RxD–
RxD+
DTR
RS-485
RS-232
CTS
TxD
RxD
10/27/2018 Page 3 / 5
126,1
https://www.phoenixcontact.com/pi/products/2702006
Communication module - AXL F RS UNI XC 1H - 2702006
Block diagram
U
Bus
Local bus
12x
5V
D
UI
E1
E2
RS-485
RS-232
µC
5V
FE
RS-485
RS-232
5V
Internal wiring of the terminal points
Approvals
Approvals
Approvals
UL Listed / cUL Listed / LR / ABS / NK / BV / DNV GL / PRS / RINA / KR / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
LR
http://www.lr.org/en
14-20019
ABS
http://www.eagle.org/eagleExternalPortalWEB/
18-HG1767360-PDA
NK
http://www.classnk.or.jp/hp/en/
14A006
10/27/2018 Page 4 / 5
https://www.phoenixcontact.com/pi/products/2702006
Communication module - AXL F RS UNI XC 1H - 2702006
Approvals
BV
http://www.veristar.com/portal/veristarinfo/generalinfo/
approved/approvedProducts/equipmentAndMaterials
36433/A2 BV
DNV GL
http://exchange.dnv.com/tari/
TAA00000DF
PRS
http://www.prs.pl/
TE/2106/880590/16
RINA
http://www.rina.org/en
ELE256518XG
KR
http://www.krs.co.kr/eng/main/main.aspx
HMB17372-AC002
cULus Listed
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
10/27/2018 Page 5 / 5