https://www.phoenixcontact.com/pi/products/2813570
Signal conditioner - MINI MCR-SL-U-I-0-SP - 2813570
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR 3-way isolating amplifier, for electrical isolation of analog signals, with spring-cage connection, input
signal: 0 V ... 10 V, output signal: 0 mA ... 20 mA
Why buy this product
Power supply possible via the foot element (TBUS)
Entry-level alternative to configurable signal conditioners
Low power consumption
Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of standard analog signals
3-way isolation
Fixed signal combinations
Key Commercial Data
Packing unit
GTIN
GTIN
4046356101936
1 pc
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
6.2 mm
93.1 mm
102.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-20 °C ... 65 °C
-40 °C ... 85 °C
10/01/2018 Page 1 / 5
https://www.phoenixcontact.com/pi/products/2813570
Signal conditioner - MINI MCR-SL-U-I-0-SP - 2813570
Technical data
Ambient conditions
Maximum altitude
≤ 2000 m
Input data
Number of inputs
Configurable/programmable
Voltage input signal
max. input voltage
Input resistance of voltage input
1
no
0 V ... 10 V
30 V
approx. 100 kΩ
Output data
Number of outputs
Configurable/programmable
Current output signal
Max. output current
Load/output load current output
Ripple
1
no
0 mA ... 20 mA
28 mA
≤ 500 Ω
< 20 mV
PP
(at 500 Ω)
Power supply
Nominal supply voltage
Supply voltage range
Max. current consumption
Power consumption
24 V DC
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN 60715))
< 28 mA
< 600 mW
Connection data
Connection method
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Stripping length
Spring-cage connection
0.2 mm²
2.5 mm²
24
12
0.2 mm²
2.5 mm²
8 mm
General
No. of channels
Maximum transmission error
Maximum temperature coefficient
Temperature coefficient, typical
Limit frequency (3 dB)
Step response (10-90%)
Electrical isolation
1
≤ 0.1 % (of final value)
< 0.01 %/K
< 0.002 %/K
approx. 100 Hz
approx. 3.5 ms
Basic insulation according to EN 61010
10/01/2018 Page 2 / 5
https://www.phoenixcontact.com/pi/products/2813570
Signal conditioner - MINI MCR-SL-U-I-0-SP - 2813570
Technical data
General
Overvoltage category
Degree of pollution
Rated insulation voltage
Test voltage, input/output/supply
Electromagnetic compatibility
Noise emission
Noise immunity
Color
Housing material
Mounting position
Assembly instructions
Conformance
ATEX
UL, USA/Canada
GL
Fire protection for rail vehicles (DIN EN 45545-2) R22
Fire protection for rail vehicles (DIN EN 45545-2) R23
Fire protection for rail vehicles (DIN EN 45545-2) R24
II
2
30 V AC
1.5 kV (50 Hz, 1 min.)
Conformance with EMC directive
EN 61000-6-4
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
green
PBT
any
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
CE-compliant
II 3 G Ex nA IIC T4 Gc X
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
GL EMC 2 D
HL 1 - HL 2
HL 1 - HL 2
HL 1 - HL 2
EMC data
Designation
Standards/regulations
Typical deviation from the measuring range final value
Designation
Standards/regulations
Typical deviation from the measuring range final value
Designation
Standards/regulations
Typical deviation from the measuring range final value
Electromagnetic RF field
EN 61000-4-3
5%
Fast transients (burst)
EN 61000-4-4
5%
Conducted interferences
EN 61000-4-6
5%
Standards and Regulations
Electromagnetic compatibility
Noise emission
Connection in acc. with standard
Designation
Standards/regulations
Designation
Standards/regulations
Conformance with EMC directive
EN 61000-6-4
CUL
Electromagnetic RF field
EN 61000-4-3
EN 61000-4-4
Conducted interferences
EN 61000-4-6
10/01/2018 Page 3 / 5
https://www.phoenixcontact.com/pi/products/2813570
Signal conditioner - MINI MCR-SL-U-I-0-SP - 2813570
Technical data
Standards and Regulations
Electrical isolation
Conformance
ATEX
UL, USA/Canada
GL
Fire protection for rail vehicles (DIN EN 45545-2) R22
Fire protection for rail vehicles (DIN EN 45545-2) R23
Fire protection for rail vehicles (DIN EN 45545-2) R24
Fire protection for rail vehicles (DIN EN 45545-2) R26
Basic insulation according to EN 61010
CE-compliant
II 3 G Ex nA IIC T4 Gc X
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
GL EMC 2 D
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
Sensor / Field
Dimensional drawing
93,1
6,2
PLC / DCS
IN
OUT
OUT U
U
S
4-wire
GND
1
+
1
IN U
OUT I
active
5
+
5
passive
2
–
2
GND 1
GND 2
6
–
6
+
3
+24V
+24V
7
+
–
4
GND 3
GND 3
8
–
+24V
GND 3
Zone 2
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / GL / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / EAC Ex / ATEX / cULus Listed
Approval details
10/01/2018 Page 4 / 5
102,5
https://www.phoenixcontact.com/pi/products/2813570
Signal conditioner - MINI MCR-SL-U-I-0-SP - 2813570
Approvals
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
GL
http://exchange.dnv.com/tari/
24916-05 HH
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com