Plug-in surge arrester for 2-phase power supply networks with separate N and PE (4-conductor system: L1, L2,
N, PE), with remote indication contact.
Product Features
■
■
■
■
■
■
■
■
■
With or without floating remote indication contact
Plugs can be checked with CHECKMASTER
High continuous voltage of 175 V AC for 120/208 V AC networks with high voltage fluctuations
Optical, mechanical status indication for the individual arresters
Disconnect device on each individual plug
Type 2 consistent plug-in surge arresters
Mechanical coding of all slots
Modular arrester blocks with ultra-narrow design
Use of varistors that are free of leakage current
Key Commercial Data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
308.1 g
85369010
Germany
Technical data
Dimensions
Height
Width
Depth
98 mm
37.25 mm
71.5 mm
04/18/2016 Page 1 / 9
https://www.phoenixcontact.com/us/products/2859495
Type 2 surge arrester - VAL-CP-2S-175 - 2859495
Technical data
Dimensions
Horizontal pitch
2 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
Shock (operation)
Vibration (operation)
IP20
-40 °C ... 80 °C
-40 °C ... 80 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
Standards/specifications
IEC test classification
EN type
IEC power supply system
Number of ports
SPD design
Mode of protection
IEC 61643-11 2011
EN 61643-11 2012
II
T2
T2
TN-S
TT
One
Combination type
L-N
L-PE
N-PE
Mounting type
Color
Housing material
Degree of pollution
Flammability rating according to UL 94
Type
Number of positions
Surge protection fault message
DIN rail: 35 mm
gray/blue
black
PBT-FR
2
V-0
DIN rail module, two-section, divisible
3
Optical, remote indicator contact
Protective circuit
Nominal voltage U
N
Nominal frequency f
N
Maximum continuous operating voltage U
C
(L-N)
120/208 V AC (TN-S)
120/208 V AC (TT)
50 Hz (60 Hz)
175 V AC
04/18/2016 Page 2 / 9
https://www.phoenixcontact.com/us/products/2859495
Type 2 surge arrester - VAL-CP-2S-175 - 2859495
Technical data
Protective circuit
Maximum continuous operating voltage U
C
(L-PE)
Maximum continuous voltage U
C
(N-PE)
Rated load current I
L
Residual current I
PE
Nominal discharge current I
n
(8/20) µs (L-N)
Nominal discharge current I
n
(8/20) µs (N-PE)
Maximum discharge current I
max
(8/20) µs (L-N)
Maximum discharge current I
max
(8/20) µs (N-PE)
Follow current interrupt rating I
fi
(N-PE)
Short-circuit current rating I
SCCR
Voltage protection level U
p
(L-N)
Voltage protection level U
p
(L-PE)
Voltage protection level U
p
(N-PE)
Residual voltage U
res
(L-N)
175 V AC
150 V AC
40 A (Biconnect M4 fork-type cable lug 6 mm²)
63 A (TWIN ferrule 2 x 10 mm²)
≤ 1 µA
20 kA
20 kA
40 kA
40 kA
100 A (150 V AC)
25 kA
≤ 0.85 kV
≤ 1.3 kV
≤ 0.95 kV
≤ 0.85 kV (at I
n
)
≤ 0.75 kV (at 10 kA)
≤ 0.65 kV (at 5 kA)
≤ 0.63 kV (at 4 kA)
≤ 0.57 kV (at 2 kA)
Residual voltage U
res
(N-PE)
≤ 0.4 kV (at I
n
)
≤ 0.4 kV (at 10 kA)
≤ 0.4 kV (at 5 kA)
≤ 0.4 kV (at 4 kA)
≤ 0.4 kV (at 2 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)
TOV behavior at U
T
(L-N)
TOV behavior at U
T
(N-PE)
Response time t
A
(L-N)
Response time t
A
(N-PE)
Max. backup fuse with branch wiring
Max. backup fuse with V-type through wiring
≤ 0.95 kV
240 V AC (5 s / withstand mode)
240 V AC (120 min / safe failure mode)
1200 V AC (200 ms / withstand mode)
≤ 25 ns
≤ 100 ns
315 A (gG)
40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²)
63 A (gG / TWIN ferrule 2x 10mm²)
Indicator/remote signaling
Connection name
Switching function
Remote fault indicator contact
PDT contact
04/18/2016 Page 3 / 9
https://www.phoenixcontact.com/us/products/2859495
Type 2 surge arrester - VAL-CP-2S-175 - 2859495
Technical data
Indicator/remote signaling
Operating voltage
Operating current
Connection method
Screw thread
Tightening torque
Stripping length
Conductor cross section flexible
Conductor cross section solid
Conductor cross section AWG
5 V AC ... 250 V AC
125 V DC (200 mA DC)
5 mA AC ... 1 A AC
1 A DC (30 V DC)
Pluggable screw connection
M2
0.25 Nm
7 mm
0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm²
28 ... 16
Connection data
Connection method
Conductor cross section flexible
Conductor cross section solid
Conductor cross section AWG
Screw thread
Tightening torque
Stripping length
Screw connection
2.5 mm² ... 16 mm²
2.5 mm² ... 25 mm²
12 ... 4
M5
4.5 Nm
16 mm
UL specifications
SPD Type
Maximum continuous operating voltage MCOV (L-L)
Maximum continuous operating voltage MCOV (L-N)
Maximum continuous operating voltage MCOV (L-G)
Maximum continuous operating voltage MCOV (N-G)
Nom. voltage
Mode of protection
4CA
350 V AC
175 V AC
175 V AC
150 V AC
120/208 V AC
L-L
L-N
L-G
N-G
Power distribution system
Nominal frequency
Measured limiting voltage MLV (L-L)
Measured limiting voltage MLV (L-N)
Measured limiting voltage MLV (L-G)
Measured limiting voltage MLV (N-G)
3Y
50/60 Hz
2010 V
1510 V
1630 V
560 V
04/18/2016 Page 4 / 9
https://www.phoenixcontact.com/us/products/2859495
Type 2 surge arrester - VAL-CP-2S-175 - 2859495
Technical data
UL specifications
Nominal discharge current I
n
(L-L)
Nominal discharge current I
n
(L-N)
Nominal discharge current I
n
(L-G)
Nominal discharge current I
n
(N-G)
Follow current (N-G)
20 kA
20 kA
20 kA
20 kA
200 A (150 V AC)
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
eCl@ss 9.0
27140201
27130801
27130801
27130801
27130805
27130805
27130805
27130805
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000941
EC000941
EC000941
EC000941
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Approvals
Approvals
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / IECEE CB Scheme / CCA / EAC / cULus Recognized
04/18/2016 Page 5 / 9