https://www.phoenixcontact.com/pi/products/2966537
Relay Module - PLC-RSP-230UC/21 - 2966537
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
PLC relay, consisting of base terminal block PLC-BSP.../21 with spring-cage connection and pluggable
miniature relay with power contact, for assembly on DIN rail NS 35/7.5, 1 PDT, input voltage 230 V AC / 220 V
DC
Why buy this product
Slim design
Efficient connection to system cabling using V8 adapter
RT III sealed relay
Safe isolation according to DIN EN 50178 between coil and contact
Integrated input circuit and interference suppression circuit
Functional plug-in bridges
Key Commercial Data
Packing unit
GTIN
GTIN
Sales Key
4017918164843
08
10 STK
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
6.2 mm
80 mm
94 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-40 °C ... 55 °C
-40 °C ... 85 °C
02/18/2018 Page 1 / 5
https://www.phoenixcontact.com/pi/products/2966537
Relay Module - PLC-RSP-230UC/21 - 2966537
Technical data
Coil side
Nominal input voltage U
N
Typical input current at U
N
Typical response time
Typical release time
Protective circuit
Operating voltage display
Power dissipation for nominal condition
230 V AC
220 V DC
3.2 mA (at U
N
= 230 V AC)
3 mA (at U
N
= 220 V DC)
7 ms
15 ms
Bridge rectifier Bridge rectifier
Yellow LED
0.74 W
Contact side
Contact type
Type of switch contact
Contact material
Maximum switching voltage
Minimum switching voltage
Min. switching current
Maximum inrush current
Limiting continuous current
Interrupting rating (ohmic load) max.
1 PDT
Single contact
AgSnO
250 V AC/DC (The separating plate PLC-ATP should be installed for
voltages larger than 250 V (L1, L2, L3) between identical terminal blocks
in adjacent modules. Potential bridging is then carried out with FBST 8-
PLC... or ...FBST 500...)
5 V (at 100 mA)
10 mA (at 12 V)
on request
6A
140 W (at 24 V DC)
20 W (at 48 V DC)
18 W (at 60 V DC)
23 W (at 110 V DC)
40 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity in acc. with DIN VDE 0660/IEC 60947
2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.1 A (at 220 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 230 V, AC15)
Connection data input side
Connection name
Connection method
Stripping length
Conductor cross section solid
Conductor cross section flexible
Conductor cross section AWG
Coil side
Spring-cage connection
8 mm
0.14 mm² ... 2.5 mm²
0.14 mm² ... 2.5 mm²
26 ... 14
02/18/2018 Page 2 / 5
https://www.phoenixcontact.com/pi/products/2966537
Relay Module - PLC-RSP-230UC/21 - 2966537
Technical data
Connection data output side
Connection name
Connection method
Stripping length
Conductor cross section solid
Conductor cross section flexible
Conductor cross section AWG
Contact side
Spring-cage connection
8 mm
0.14 mm² ... 2.5 mm²
0.14 mm² ... 2.5 mm²
26 ... 14
General
Test voltage relay winding/relay contact
Operating mode
Degree of protection
Mechanical service life
Mounting position
Assembly instructions
4 kV AC (50 Hz, 1 min.)
100% operating factor
IP20 (Relay base)
2 x 10 cycles
any
In rows with zero spacing
7
Standards and Regulations
Connection in acc. with standard
Designation
Standards/regulations
Degree of pollution
Overvoltage category
Flammability rating according to UL 94
CUL
Standards/regulations
IEC 60664
EN 50178
3
III
V0
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Diagram
Circuit diagram
A2
A1
11
14
12
Interrupting rating
02/18/2018 Page 3 / 5
https://www.phoenixcontact.com/pi/products/2966537
Relay Module - PLC-RSP-230UC/21 - 2966537
Approvals
Approvals
Approvals
UL Recognized / UL Listed / cUL Recognized / cUL Listed / GL / EAC / RC FRT / EAC / PRS / cULus Recognized / cULus Listed
Ex Approvals
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 172140
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 172140
GL
http://exchange.dnv.com/tari/
46016-03 HH
EAC
RU C-
DE.A*30.B.01082
RC FRT
http://www.rsfgt.ru/en/web/guest/english
B.00094
EAC
EAC-Zulassung
02/18/2018 Page 4 / 5
https://www.phoenixcontact.com/pi/products/2966537
Relay Module - PLC-RSP-230UC/21 - 2966537
Approvals
PRS
http://www.prs.pl/
TE/2109/880590/16
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
cULus Listed
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
02/18/2018 Page 5 / 5