Key Commercial Data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
106.5 g
85363010
Germany
Technical data
Dimensions
Height
Width
Depth
144.7 mm
12.35 mm
84.5 mm
Ambient conditions
Ambient temperature (operation)
Degree of protection
-20 °C ... 60 °C
IP20
General
Housing material
Flammability rating according to UL 94
Color
Standards for cearances and creepage distances
Mounting type
PBT
V2
black
VDE 0110-1
IEC 60664-1
DIN rail: 35 mm
04/18/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2858386
Surge protection device - TT-PI-EX-TB - 2858386
Technical data
General
Type
Number of positions
Direction of action
PI basic terminal block
2
Line-Line & Line-Earth Ground
Protective circuit
IEC test classification
C1
C2
C3
D1
Nominal voltage U
N
Maximum continuous voltage U
C
Maximum continuous voltage U
C
(wire-wire)
Nominal current I
N
Operating effective current I
C
at U
C
Residual current I
PE
Nominal discharge current I
n
(8/20) µs (Core-Core)
Nominal discharge current I
n
(8/20) µs (Core-Earth)
Total surge current (8/20) µs
Max. discharge current I
max
(8/20) µs maximum (Core-Core)
Max. discharge current I
max
(8/20) µs maximum (Core-Earth)
Nominal pulse current Ian (10/1000) µs (Core-Core)
Nominal pulse current Ian (10/1000) µs (Core-Earth)
Impulse discharge current (10/350)½µs, peak value l
imp
Output voltage limitation at 1 kV/µs (Core-Earth) spike
Output voltage limitation at 1 kV/µs (Core-Core) static
Residual voltage at I
n
(conductor-conductor)
Residual voltage with Ian (10/1000)µs (conductor-conductor)
Voltage protection level U
p
(core-core)
Voltage protection level U
p
(core-ground)
Response time tA (Core-Core)
Response time tA (Core-Earth)
Input attenuation aE, sym.
Cut-off frequency fg (3 dB), sym. in 50 Ohm system
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
24 V DC
30 V DC
21 V AC
30 V DC
21 V AC
250 mA (40°C)
≤ 5 µA
≤ 4 µA
5 kA
5 kA
10 kA
5 kA
5 kA
100 A
100 A
1 kA
1.85 kV
≤ 45 V
≤ 45 V
≤ 45 V
≤ 90 V (C2 - 10 kV/5 kA)
≤ 1.85 kV (C2 - 10 kV/5 kA)
≤ 1 ns
≤ 100 ns
0.8 dB (≤ 1 MHz / 50 Ω)
0.3 dB (≤ 250 kHz / 150 Ω)
typ. 7 MHz
typ. 2 MHz
04/18/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2858386
Surge protection device - TT-PI-EX-TB - 2858386
Technical data
Protective circuit
Resistance in series
Surge protection fault message
Impulse durability (conductor-conductor)
Impulse durability (conductor-ground)
4.7 Ω ±10 %
None
C2 - 10 kV/5 kA
C3 - 100 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 1 kA
Connection data
Connection method
Connection type IN
Connection type OUT
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Screw connection
Screw terminal blocks
Screw terminal blocks
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
14
Standards and Regulations
Standards/regulations
IEC 61643-21
EN 50020
General
Maximum inner capacitance C
i
Maximum inner inductance L
i
Maximum inner time factor (R
i
/L
i
)
Max. input current I
i
Max. input voltage U
i
3 nF
1 µH
0.1 µs
250 mA
30 V
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
27140201
27130801
27130801
27130801
27130807
27130807
04/18/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2858386
Surge protection device - TT-PI-EX-TB - 2858386
Classifications
eCl@ss
eCl@ss 8.0
eCl@ss 9.0
27130807
27130807
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000943
EC000943
EC000943
EC000943
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Accessories
Accessories
Bridge
Continuous plug-in bridge - FBST 500-PLC RD - 2966786
Continuous plug-in bridge, Length: 500 mm, Color: red
Continuous plug-in bridge - FBST 500-PLC BU - 2966692
Continuous plug-in bridge, Length: 500 mm, Color: blue
04/18/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2858386
Surge protection device - TT-PI-EX-TB - 2858386
Accessories
Continuous plug-in bridge - FBST 500-PLC GY - 2966838
Continuous plug-in bridge, Length: 500 mm, Color: gray
Labeled terminal marker
Marker for terminal blocks - ZBFM 6/WH,LGS:1-100 - 0800284
Marker for terminal blocks, Sheet, white, labeled, Printed horizontally: Consecutive numbers from 1 - 100, Mounting type:
Snap into flat marker groove, for terminal block width: 6.2 mm, Lettering field: 5 x 5.5 mm
Flat zack marker sheet - ZBFM 6/WH,LGS:FORTL.ZAHLEN - 0803621
Flat zack marker sheet, Sheet, white, labeled, Printed horizontally: Consecutive numbers from 1 - 10, 11 - 20, etc. up to
91 - 100, Mounting type: Snap into flat marker groove, for terminal block width: 6.2 mm, Lettering field: 5 x 5.5 mm
Terminal marking
Flat zack marker sheet - ZBFM 6/WH:UNBEDRUCKT - 0803618
Flat zack marker sheet, Sheet, white, unlabeled, can be labeled with: Plotter, Mounting type: Snap into flat marker
groove, for terminal block width: 6.2 mm, Lettering field: 5 x 5.5 mm
Additional products
04/18/2016 Page 5 / 6