Technical Data
720099
Effective October 2017
Supersedes September 2015
BUSSMANN
SERIES
400 Volts gG/gL NH Fuse links
Product description
Eaton’s Bussmann
®
series 400 V a.c. NH square
bodied industrial fuse links are suitable for a
wide variety of applications.
Standard features
•
•
•
•
Reliable dual indicator system
Low temperature rise
Globally compliant
Compatible with Eaton’s Bussmann series
NH bases and NH Fuse gear
Technical Data
720099
Effective October 2017
400 Volts gG/gL NH Fuse links
Microswitches
NH Fuse link
body size
Suitable microswitch
Catalogue symbol:
•
•
(amp)NHG(size)B-400 with conducting metal gripping lugs
(amp(NHG(size)BI-400 with insulated metal gripping lugs
000
170H0236
170H0236
170H0235
170H0236
BVL50
170H0235 or 170H0236
BVL50
170H0235
Fuse body size:
•
00
01
1
02
2
03
3
000 to 3
Technical data:
•
•
•
•
•
Volts: 400 V a.c.
Amps: 2 to 630 A
Breaking capacity: 120 kA AC
Operating frequency: 45-62 Hz
Class of operation: gG/gL
Compatible fuse holders and fuse gear
Description
Type
Data sheet number
Standards/Approvals:
•
•
•
•
Fuse bases 1-pole
Fuse bases 3-pole
Fuse bases accessories
Fuse rails
DIN-Rail mounting SD-D
Screw mounting SD-S
DIN-Rail mounting TD-D
IP20, Shroud and phase
barriers kits
Vertical EBF
Vertical EBV
Horizontal - EBH size 000
Horizontal - EBH sizes 00
to 4
10163
10163
10163
10163
10240
10275
10292
10293
IEC 60269
VDE 0636
DIN 43620
CE
Fuse switch
disconnectors
Packaging:
•
Sizes 000 to 3: 3 per carton
Size - mm
Table 1. NH Sizes
Size
000
00
01
1
02
2
03
3
a1
78.5 ± 1.5
78.5 ± 1.5
135±2.5
135±2.5
150±2.5
150±2.5
150±2.5
150±2.5
a2
(max)
54
54
75
75
75
75
75
75
a3
45±1.5
45±1.5
62±2.5
62±2.5
62±2.5
62±2.5
62±2.5
62±2.5
a4
49±1.5
49±1.5
68±2.5
68±2.5
68±2.5-
68±2.5
68±2.5
68±2.5
b
15
15
15
20
20
25
25
32
c1
35
35
40
40
48
48
60
60
c2
10
11
11
11
11
11
11
11
d
2±0.5
2±0.5
2.5±0.5
2.5±0.5
2.5±0.5
2.5±0.5
2.5±0.5
3±0.5
e1
(max)
41
48
48
53
53
61
61
75
e2
(max)
21
30
30
40
40
53
53
70
e3
(max)
16
25
25
25
25
25
25
25
e4
6
6
6
6
6
6
6
6
f
(max)
8
15
15
15
15
15
15
18
2
EATON
www.eaton.com
Technical Data
720099
400 Volts gG/gL NH Fuse links
Table 2. Part numbers
Effective October 2017
Size
000
00
01
1
02
2
03
3
Rated
current
(Amps)
2
4
6
10
16
20
25
32
35
40
50
63
80
100
125
160
35
40
50
63
80
100
125
160
200
224
250
35
40
50
63
80
100
125
160
200
224
250
315
355
400
630
250
315
355
400
500
630
Rated
voltage
(V a.c.)
400
gG/gL dual indicator
Voltage conducting
metal gripping lugs
2NHG000B-400
4NHG000B-400
6NHG000B-400
10NHG000B-400
16NHG000B-400
20NHG000B-400
25NHG000B-400
32NHG000B-400
35NHG000B-400
40NHG000B-400
50NHG000B-400
63NHG000B-400
80NHG000B-400
100NHG000B-400
125NHG00B-400
160NHG00B-400
35NHG01B-400
40NHG01B-400
50NHG01B-400
63NHG01B-400
80NHG01B-400
100NHG01B-400
125NHG01B-400
160NHG01B-400
200NHG1B-400
224NHG1B-400
250NHG1B-400
35NHG02B-400
40NHG02B-400
50NHG02B-400
63NHG02B-400
80NHG02B-400
100NHG02B-400
125NHG02B-400
160NHG02B-400
200NHG02B-400
224NHG02B-400
250NHG02B-400
315NHG2B-400
355NHG2B-400
400NHG2B-400
630NHG2B-400
250NHG03B-400
315NHG03B-400
355NHG03B-400
400NHG03B-400
500NHG3B-400
630NHG3B-400
Insulated metal
gripping lugs
2NHG000BI-400
4NHG000BI-400
6NHG000BI-400
10NHG000BI-400
16NHG000BI-400
20NHG000BI-400
25NHG000BI-400
32NHG000BI-400
35NHG000BI-400
40NHG000BI-400
50NHG000BI-400
63NHG000BI-400
80NHG000BI-400
100NHG000BI-400
125NHG00BI-400
160NHG00BI-400
35NHG01BI-400
40NHG01BI-400
50NHG01BI-400
63NHG01BI-400
80NHG01BI-400
100NHG01BI-400
125NHG01BI-400
160NHG01BI-400
200NHG1BI-400
224NHG1BI-400
250NHG1BI-400
35NHG02BI-400
40NHG02BI-400
50NHG02BI-400
63NHG02BI-400
80NHG02BI-400
100NHG02BI-400
125NHG02BI-400
160NHG02BI-400
200NHG02BI-400
224NHG02BI-400
250NHG02BI-400
315NHG2BI-400
355NHG2BI-400
400NHG2BI-400
-
250NHG03BI-400
315NHG03BI-400
355NHG03BI-400
400NHG03BI-400
500NHG3BI-400
630NHG3BI-400
Pack
quantity
3
* Available upon request
EATON
www.eaton.com
3
Technical Data
720099
400 Volts gG/gL NH Fuse links
Time-current curves - NH Size 000
Effective October 2017
Time in seconds (s)
Current in Amps (A)
Technical data - NH size 000
I
2
t (Amps
2
Seconds)
Fuse link
size
000
Rated
current
(Amps)
2
4
6
10
16
20
25
32
35
40
50
63
80
100
Rated
voltage
(V a.c.)
400
Minimum
pre-arcing
3.5
6
14
60
240
584
1000
2400
2900
4000
4000
6000
9900
18,100
*I
1
120kA
at 400 V a.c.
5.5
10.5
19
175
710
1800
2800
9600
11,300
16,400
12,000
20,400
35,700
39,800
Net weight
per fuse
(kg)
0.133
Part numbers
Part numbers
with insulated
with metal
metal gripping
gripping lugs
lugs
2NHG000B-400
2NHG000BI-400
4NHG000B-400
4NHG000BI-400
6NHG000B-400
6NHG000BI-400
10NHG000B-400 10NHG000BI-400
16NHG000B-400 16NHG000BI-400
20NHG000B-400 20NHG000BI-400
25NHG000B-400 25NHG000BI-400
32NHG000B-400 32NHG000BI-400
35NHG000B-400 35NHG000BI-400
40NHG000B-400 40NHG000BI-400
50NHG000B-400 50NHG000BI-400
63NHG000B-400 63NHG000BI-400
80NHG000B-400 80NHG000BI-400
100NHG000B-400 100NHG000BI-400
Watts loss
0.8
1.4
2.2
1.5
2.3
2.2
3.1
2.8
2.8
3
3.4
4.5
4.7
5.2
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
EATON
www.eaton.com
4
Technical Data
720099
Effective October 2017
400 Volts gG/gL NH Fuse links
Time-current curves - NH Size 00
Time in seconds (s)
Current in Amps (A)
Technical data - NH size 00
I
2
t (Amps
2
Seconds)
Rated
current
(Amps)
125
160
Rated
voltage
(V a.c.)
400
Minimum
pre-arcing
25,000
60,000
*I
1
120kA
at 400 V a.c.
80,000
126,000
Net weight
per fuse
(kg)
0.185
Part numbers
Part numbers
with insulated
with metal
metal gripping Fuse link
gripping lugs
lugs
size
125NHG00B-400 125NHG00BI-400
00
160NHG00B-400 160NHG00BI-400
Watts loss
8
7.8
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
5
EATON
www.eaton.com