Product data sheet
Characteristics
TWDNOI10M3
AS-Interface master module - M3 (7.3
analogue profile) V2.11 - 29.5..31.6 V DC
Main
Range of product
Product or component
type
Product compatibility
Modicon M238 logic controller
Twido
AS-Interface master module
TWDLCAA24DRF
TWDLCAA40DRF
TWDLCAE40DRF
TWDLCDA24DRF
TWDLCDA40DRF
TWDLCDE40DRF
TWDLMDA20DRT
TWDLMDA20DTK
TWDLMDA20DUK
TWDLMDA40DTK
TWDLMDA40DUK
AS-Interface M3 (7.3 analogue profile) V2.11
Standard and extended
29.5...31.6 V DC
<= 7 for analogue module
<= 62 for discrete module
<= 248 for slaves in bank A and B
<= 124 for standards slaves
<= 186 for slaves in bank A and B
<= 124 for standards slaves
Bus type
Addressing
[Us] rated supply volt-
age
Number of slave
Number of inputs
Number of outputs
Complementary
Supply
Electrical connection
Current consumption
Power dissipation in W
Number of modules per base controller
AS-i cabling system cycle time
External supply
Removable screw terminal block (power supply)
80 mA at 5 V DC
0.54 W at 24 V DC
2
5 ms with 31 slave(s)
3 ms
10 ms with 62 slave(s)
0.156 x (1 + N) ms with 20...62 slave(s)
<= 300 m with 2 repeaters ASIRPT01
<= 200 m with line extension TCSARR01M
<= 200 m with 1 repeater ASIRPT01
<= 100 m
3 LEDs (green) for output channel
3 LEDs (green) for input channel
1 LED (red) for unconnected mode (OFF)
1 LED (red) for configuration error (FLT)
1 LED (green) for module power (PWR)
1 LED (green) for local mode (LMO)
1 LED (green) for connected mode (CMO)
0.085 kg
Length of segment
Status LED
Product weight
Environment
Product certifications
IP degree of protection
Ambient air temperature for operation
Ambient air temperature for storage
AS-Interface No 47801
IP20
0...55 °C
-25...70 °C
Nov 4, 2015
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.