https://www.phoenixcontact.com/pi/products/2900443
Relay base - PLC-BPT- 5DC/21 - 2900443
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
6.2 mm PLC basic terminal block with push-in connection, without relay or solid-state relay, for mounting on
DIN rail NS 35/7,5, 1 PDT, input voltage 5 V DC
Key Commercial Data
Packing unit
GTIN
GTIN
4046356507585
10 pc
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
6.2 mm
80 mm
94 mm
Input data
Nominal input voltage U
N
Status display
Protective circuit
5 V DC
LED
Damping diode, polarity protection diode
Damping diode
Connection data, input side
Connection name
Connection method
Stripping length
Conductor cross section solid
Input side
Push-in connection
10 mm
0.14 mm² ... 2.5 mm²
11/26/2018 Page 1 / 3
https://www.phoenixcontact.com/pi/products/2900443
Relay base - PLC-BPT- 5DC/21 - 2900443
Technical data
Connection data, input side
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² ()
2x 0.5 mm² ... 1 mm² ()
Conductor cross section AWG
26 ... 14
Connection data, output side
Connection name
Connection method
Stripping length
Conductor cross section solid
Conductor cross section flexible
Output side
Push-in connection
10 mm
0.14 mm² ... 2.5 mm²
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² ()
2x 0.5 mm² ... 1 mm² ()
Conductor cross section AWG
26 ... 14
General
Note
Protective circuit
Color
Operating mode
Mounting position
Separating plate PLC-ATP must be installed for voltages larger than 250
V (L1, L2, L3) between identical terminal blocks in adjacent modules.
Potential bridging is then carried out with FBST 8-PLC... or FBST 500....
Damping diode, polarity protection diode
green
100% operating factor
any
Standards and Regulations
Connection in acc. with standard
Flammability rating according to UL 94
CUL
V0
Environmental Product Compliance
REACh SVHC
China RoHS
Lead 7439-92-1
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Approvals
Approvals
Approvals
DNV GL / UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
11/26/2018 Page 2 / 3
https://www.phoenixcontact.com/pi/products/2900443
Relay base - PLC-BPT- 5DC/21 - 2900443
Approvals
Approval details
DNV GL
http://exchange.dnv.com/tari/
TAE0000196-01
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
EAC
RU C-
DE.A*30.B.01082
cULus Recognized
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com