Notes: 1. The relay operates in a range of 80% to 110% V of the nominal voltage, but ideally, in consideration of temporary voltage fluctuations, it should be operated at the
rated voltage.
In particular, for AC operation, if the applied voltage drops to 80% V or more below the nominal voltage, humming will occur and a large current will flow leading
possibly to coil burnout.
2. The maximum applied voltage is the maximum voltage fluctuation value for the coil power supply. This value is not a permissible value for continuous operation.
(This value differs depending on the ambient temperature. Please contact us for details.)
2) DC coils (at 20°C
68°F)
Nominal coil
voltage
6V DC
12V DC
24V DC
48V DC
100/110V DC
Nominal coil current
(mA)
150
75
37
18.5
10
0.9
Nominal operating
power (W)
Coil resistance
(Ω)
40
160
650
2,600
10,000
80%V or less of
nominal voltage
(Initial)
10%V or more of
nominal voltage
(Initial)
110%V of
nominal voltage
Pick-up voltage
(at 20°C
68°F)
Drop-out voltage
(at 20°C
68°F)
Max. applied voltage
(at 70°C
158°F)
1.0
Notes: 1. The nominal operating current is
±10%
(20°C
68°F).
2. The coil resistance for DC operation is the value measured when the coil temperature is 20°C
68°F.
Compensate
±0.4%
for every
±1°C
change in temperature.
3. The relay operates in a range of 80% to 110% V of the nominal voltage, but ideally, in consideration of temporary voltage fluctuations, it should be operated at the
nominal voltage.
4. For use with 200 V DC, connect a 10 KΩ (5W) resistor, in series, to the 100 V DC relay.
5. The maximum applied voltage is the maximum voltage fluctuation value for the coil power supply. This value is not a permissible value for continuous operation.
(This value differs depending on the ambient temperature. Please contact us for details.)
2. Specifications
Characteristics
Contact
Item
Contact resistance (Initial)
Contact material
Nominal switching capacity*
4
Min. switching capacity (Reference value)*
1
Insulation resistance (Initial)
Between open contacts
Between contact sets
Between contact and coil
Temperature rise (coil)
Breakdown voltage
(Initial)
Electrical
characteristics
Operate time (at 20°C
68°F)*
2
Release time (at 20°C
68°F)*
2
Shock resistance
Mechanical
characteristics
Vibration resistance
Mechanical
Expected life
AC load
Electrical
DC load
Conditions for operation, transport and storage*
3
Max. Operating speed
Unit weight
Functional
Destructive
Functional
Destructive
Specifications
Max. 50 mΩ (By voltage drop 6 V DC 1A)
AgSnO
2
type
1 Form C: 15A 125V AC, 10A 250V AC (resistive load)
2 Form C: 10A 250V AC (resistive load)
100mA 5V DC
Min. 100MΩ (at 500V DC) Measurement at same location as “Breakdown voltage” section.
1,000 Vrms for 1min. (Detection current: 10mA)
1,500 Vrms for 1min. (Detection current: 10mA)
2,000 Vrms for 1min. (Detection current: 10mA)
Max. 80°C
176°F
(By resistive method, nominal voltage)
DC type/AC type: Max. 25ms
(Nominal coil voltage applied to the coil, excluding contact bounce time.)
DC type/AC type: Max. 25ms
(Nominal coil voltage applied to the coil, excluding contact bounce time.) (without diode)
Min. 196 m/s
2
(Half-wave pulse of sine wave: 11 ms; detection time: 10µs.)
Min. 980 m/s
2
(Half-wave pulse of sine wave: 6 ms.)
10 to 55 Hz at double amplitude of 1 mm (Detection time: 10µs.)
10 to 55 Hz at double amplitude of 2 mm
AC type: 5×10
7
(at 180 times/min.), DC type: 10
8
(at 180 times/min.)
1 Form C: 15A 125V AC, 10A 250V AC resistive load (cosϕ=1) Life switching cycle: Min. 5×10
5
2 Form C: 10A 250V AC resistive load (cosϕ=1) Life switching cycle: Min. 3×10
5
1 Form C: 3A 30V DC resistive load (cosϕ=1) Life switching cycle: Min. 5×10
5
2 Form C: 3A 30V DC resistive load (cosϕ=1) Life switching cycle: Min. 5×10
5
Ambient temperature: –50°C to +70°C
–58°F to +158°F
(Without LED indication);
–50°C to +60°C
–58°F to +140°F
(With LED indication)
Humidity: 5 to 85% R.H. (Not freezing and condensing at low temperature)
20 times/min. (at max. rating)
Approx. 35g
1.23 oz
Rating
Conditions
Notes: If integrating into electrical appliances that will be subject to compliance to the Electrical Appliance and Material Safety Law, please use in an ambient temperature
between –50°C to +40°C
–58°F to +104°F
(AC type).
*1. This value can change due to the switching frequency, environmental conditions and desired reliability level, therefore it is recommended to check this with the
actual load.
*2. For the AC coil types, the operate/release time will differ depending on the phase.
*3. The upper limit of the ambient temperature is the maximum temperature that can satisfy the coil temperature rise value. Refer to Usage, transport and storage
conditions in NOTES.
*4. When using the socket, be sure to verify the max. continuous current.