https://www.phoenixcontact.com/us/products/2951911
Relay Module - EMG 22-REL/KSR- 60/21 - 2951911
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Relay module, with soldered-in miniature switching relay, contact (AgNi): Medium to large loads, 1 PDT, input
voltage 60 V AC/DC
The illustration shows version EMG
22-REL/KSR- 24/21, with soldered-in
miniature switching relay
Product Features
Safe isolation according to DIN EN 50178 between coil and contact
Integrated input circuit and interference suppression circuit
Packing unit
GTIN
1 pc
Key commercial data
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
65.13 GRM
85364190
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
22.5 mm
75 mm
62.5 mm
10/22/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2951911
Relay Module - EMG 22-REL/KSR- 60/21 - 2951911
Technical data
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-20 °C ... 50 °C
-20 °C ... 70 °C
Coil side
Nominal input voltage U
N
Input voltage range in reference to U
N
Typical input current at U
N
Typical response time
Typical release time
Operating voltage display
Protective circuit
60 V AC/DC
0.8 ... 1.1
8 mA
8 ms
10 ms
Yellow LED
Bridge rectifier Bridge rectifier
Contact side
Contact type
Contact material
Maximum switching voltage
Maximum inrush current
Limiting continuous current
Interrupting rating (ohmic load) max.
Single contact, 1-PDT
AgNi
250 V AC/DC
8A
6A
144 W (at 24 V DC)
58 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
1500 VA (for 250 V AC)
General
Test voltage relay winding/relay contact
Test voltage relay contact/relay contact
Operating mode
Degree of protection
Mechanical service life
Standards/regulations
Rated surge voltage / insulation
Rated insulation voltage
Pollution degree
Surge voltage category
Mounting position
Assembly instructions
5 kV
rms
(50 Hz, 1 min.)
1 kV AC (50 Hz, 1 min.)
100% operating factor
IP20
Approx. 5 x 10 cycles
EN 50178
4 kV / Basic isolation, (safe isolation, reinforced insulation and 6 kV
between input circuit and output contact current paths.)
260 V AC
2
III
any
In rows with zero spacing
10/22/2014 Page 2 / 4
7
https://www.phoenixcontact.com/us/products/2951911
Relay Module - EMG 22-REL/KSR- 60/21 - 2951911
Technical data
Connection data
Connection method
Stripping length
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG/kcmil max
Conductor cross section AWG/kcmil min.
Screw thread
Screw connection
8 mm
0.2 mm²
2.5 mm²
0.2 mm²
4 mm²
12
24
M3
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27371102
27371102
27371001
27371001
27371001
27371001
27371001
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000196
EC000196
EC000196
EC000196
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30211916
39121515
39121515
39121515
39121515
Drawings
10/22/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2951911
Relay Module - EMG 22-REL/KSR- 60/21 - 2951911
Circuit diagram
12
A1
A1
14
A2
A2
11 11
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
10/22/2014 Page 4 / 4