760134981 | P-024-OZ-5K-FSUBK
LazrSPEED® Indoor/Outdoor Plenum Distribution Cable, interlocking
aluminum armored with plenum jacket, 24 fiber single-unit
Product Classification
Portfolio
Product Type
Regional Availability
CommScope®
Fiber indoor/outdoor cable
Asia | Australia/New Zealand | EMEA | Latin America | North America
Standards And Qualifications
Cable Qualification Standards
ANSI/ICEA S-104-696 | Telcordia GR-20 (water penetration for internal cable) | Telcordia GR-
409
Representative Image
General Specifications
Construction Type
Cable Type
Armored
Distribution
Construction Materials
Fiber Type Solution
Total Fiber Count
OM4, LazrSPEED® 550
24
page 1 of 3
March 30, 2019
©2019 CommScope, Inc. All rights reserved. All trademarks identified by ® or ™ are registered trademarks,
respectively, of CommScope.All specifications are subject to change without notice. See www.commscope.com for the
most current information. Revised: February 4, 2019
760134981 | P-024-OZ-5K-FSUBK
Armor Type
Fiber Type
Fiber Type, quantity
Jacket Color
Jacket UV Resistance
Interlocking aluminum
OM4, LazrSPEED® 550
24
Black
UV stabilized
Dimensions
Cable Weight
Diameter Over Armor
Diameter Over Jacket
146.0 lb/kft | 218.0 kg/km
13.34 mm | 0.53 in
15.40 mm | 0.61 in
Physical Specifications
Minimum Bend Radius, loaded
Minimum Bend Radius, unloaded
30.7 cm | 12.1 in
21.5 cm | 8.5 in
Tensile Load, long term, maximum
90 lbf | 400 N
Tensile Load, short term, maximum
300 lbf | 1335 N
Vertical Rise, maximum
187.0 m | 613.5 ft
Flame Test Specifications
Flame Test Listing
Flame Test Method
NEC OFCP (ETL) and c(ETL)
NFPA 262
Environmental Specifications
Environmental Space
Installation Temperature
Operating Temperature
Storage Temperature
Plenum
-30 °C to +70 °C (-22 °F to +158 °F)
-40 °C to +70 °C (-40 °F to +158 °F)
-40 °C to +75 °C (-40 °F to +167 °F)
Mechanical Test Specifications
Compression
Compression Test Method
Flex
Flex Test Method
Impact
Impact Test Method
Strain
Strain Test Method
Twist
485 lb/in | 85 N/mm
FOTP-41 | IEC 60794-1 E3
25 cycles
FOTP-104 | IEC 60794-1 E6
25.80 ft lb | 35.00 N-m
FOTP-25 | IEC 60794-1 E4
See long and short term tensile loads
FOTP-33 | IEC 60794-1 E1
10 cycles
page 2 of 3
March 30, 2019
©2019 CommScope, Inc. All rights reserved. All trademarks identified by ® or ™ are registered trademarks,
respectively, of CommScope.All specifications are subject to change without notice. See www.commscope.com for the
most current information. Revised: February 4, 2019
760134981 | P-024-OZ-5K-FSUBK
Twist Test Method
Water Penentration
Water Penentration Test Method
FOTP-85 | IEC 60794-1 E7
24 h
FOTP-82 | IEC 60794-1 F5
Environmental Test Specifications
Cable Freeze Test Method
Heat Age
Heat Age Test Method
Low High Bend
Low High Bend Test Method
Temperature Cycle
Temperature Cycle Test Method
IEC 60794-1 F15
-40 °C to +85 °C (-40 °F to +185 °F)
IEC 60794-1 F9
-40 °C to +70 °C (-40 °F to +158 °F)
FOTP-37 | IEC 60794-1 E11
-40 °C to +70 °C (-40 °F to +158 °F)
FOTP-3 | IEC 60794-1 F1
Regulatory Compliance/Certifications
Agency
RoHS 2011/65/EU
ISO 9001:2015
Classification
Compliant
Designed, manufactured and/or distributed under this quality management system
Included Products
CS -5K-TB (Product Component—not orderable)
—
LazrSPEED ® 550 OM4 Bend-Insensitive Multimode Fiber
CS-5K-
Component—
LazrSPEED®
Bend-
* Footnotes
Operating Temperature
Specification applicable to non-terminated bulk fiber cable
page 3 of 3
March 30, 2019
©2019 CommScope, Inc. All rights reserved. All trademarks identified by ® or ™ are registered trademarks,
respectively, of CommScope.All specifications are subject to change without notice. See www.commscope.com for the
most current information. Revised: February 4, 2019