Zelio
®
Relays
RSL Slim Interface Plug-In Relays
Catalog
8501CT0901
2009
Class 8501
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Zelio RSL Relay Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Anatomy of a Zelio RSL Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
RSL Slim Interface Plug-In Relays
Introduction
Introduction
Zelio
®
RSL slim interface plug-in relays are both compact in size and modular in design. At only
0.24 in. (6 mm) wide, RSL relays save valuable space when mounted on a DIN rail at the back of
an enclosure.
Zelio RSL Relay Options
Pre-assembled: A single unit composed of a standard relay mounted on a socket
•
•
Standard features:
The socket includes a built-in protection circuita and an LED indicator.
Wire connection options:
— Screw connectors
— Spring terminals
•
Robust solution:
Product range covers a wide variety of operating voltages (12–230 V).
Custom-assembled: Individual relays and sockets
•
•
Flexibility for custom applications:
The relay and the socket are available separately, to meet various application requirements.
Simple maintenance:
An RSL slim interface relay can be replaced without disconnecting the socket wiring.
a
Provides protection against reverse polarity and surge voltages as specified in this catalog.
© 2009 Schneider Electric
All Rights Reserved
3
12/2009
RSL Slim Interface Plug-In Relays
Anatomy of a Zelio RSL Relay
Anatomy of a Zelio RSL Relay
Figure 1:
Pre-assembled RSL Slim Interface Relay
A
B
A. 6 A relay with one C/O contact
B. Retention lever for easy removal of the
relay from its socket
C. Sockets offer wire connection with either
screw connectors or spring terminals
D. Sockets have a built-in protection circuit
and an LED indicator
D
C
Figure 2:
RSL Slim Interface Relay
E. Five flat, reinforced PCB pins
E
Figure 3:
Socket for RSL Slim Interface Relay
G
F
H
F. Five female contacts for the relay pins
G. Retention lever that accepts optional
ID tags
H. Wire connection by screw connector or
spring terminals
I.
Protection circuit and LED indicator
(built into the socket)
I
J. Locating slot for mounting on DIN rail
J
4
12/2009
© 2009 Schneider Electric
All Rights Reserved
RSL Slim Interface Plug-In Relays
Characteristics
Characteristics
Table 1:
General Characteristics
IEC 61810-1, UL 508, CSA C22-2 No. 14
UL E173076, UL E172326
CSA 240278, CSA 247510
GOST
-40 to +185 °F (-40 to +85 °C)
-40 to +131 °F (-40 to +55 °C)
10 gn
5 gn
IP 40 (Relays)
IP 20 (Sockets)
10 gn
5 gn
RT III (conforms to IEC 61810-1)
Any
Conforming to Standards
Product Certifications
Ambient Air Temperature
(Around the device)
Vibration Resistance
(conforming to IEC/EN 60068-2-6)
Degree of Protection
(Conforming to IEC/EN 60529)
Shock Resistance
(Conforming to IEC/EN 60068-2-27)
Protection Category
Mounting Position
Opening
Closing
Storage
Operation
In operation
Not operating
Table 2:
Insulation Characteristics
250 V (IEC)
6 kV
4000 V
1000 V
Rated Insulation Voltage (Ui)
Rated Impulse Withstand Voltage (Uimp)
Between coil and contact
Dielectric Strength
(rms voltage)
Between contacts
© 2009 Schneider Electric
All Rights Reserved
5