https://www.phoenixcontact.com/hq/products/2801636
Lightning current arrester type 1 - FLT 35 CTRL-4.0/I - 2801636
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Type 1/Class I/B arrester (lightning current arrester) with encapsulated arc chopping spark gap and ignition
electronics with control lamp, single-channel. Voltage protection level: 4 kV. Housing width: 17.5 mm (1 HP)
Key Commercial Data
Packing unit
GTIN
GTIN
Custom tariff number
Note
4046356907668
85363030
Made to Order (non-returnable)
1 STK
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
88.6 mm
17.6 mm
66.2 mm
1 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
IP20 (only when all terminal points are used)
-40 °C ... 85 °C
-40 °C ... 85 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
General
IEC test classification
EN type
IEC power supply system
I
T1
T1
TT
11/15/2016 Page 1 / 3
https://www.phoenixcontact.com/hq/products/2801636
Lightning current arrester type 1 - FLT 35 CTRL-4.0/I - 2801636
Technical data
General
TN-S
Number of ports
SPD design
Mode of protection
Mounting type
Color
Housing material
Degree of pollution
Flammability rating according to UL 94
Design
Number of positions
Surge protection fault message
One
Voltage-switching type
L-PEN
DIN rail: 35 mm
black
PA 6.6
2
V-0
Rail-mountable module, one-piece
1
optical
Additional descriptions
Note
100 % lightning impulse sparkover voltage (1.2/50) µs ≤ 1.5 kV
Protective circuit
Nominal voltage U
N
Nominal frequency f
N
Maximum continuous operating voltage U
C
(L-PEN)
Rated load current I
L
Residual current I
PE
Standby power consumption P
C
Impulse discharge current (10/350) µs (L-PEN), charge
Impulse discharge current (10/350) µs (L-PEN), specific energy
Impulse discharge current (10/350) µs (L-PEN), peak current value I
imp
Follow current interrupt rating I
fi
(L-PEN)
Short-circuit current rating I
SCCR
Voltage protection level U
p
(L-PEN)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PEN)
TOV behavior at U
T
(L-PEN)
Response time t
A
(L-PEN)
Max. backup fuse with branch wiring
Max. backup fuse with V-type through wiring
230/400 V AC (TN)
230/400 V AC (TT)
50 Hz (60 Hz)
260 V AC
80 A
≤ 2.5 mA
≤ 650 mVA
17.5 As
306 J/Ω
35 kA
3 kA
3 kA
≤ 4 kV
≤ 4 kV
440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
≤ 100 ns
400 A AC (gG)
80 A AC (gG)
Connection data
Connection method
Screw thread
Tightening torque
Stripping length
Screw terminal blocks
M5
4.5 Nm
14.5 mm
11/15/2016 Page 2 / 3
https://www.phoenixcontact.com/hq/products/2801636
Lightning current arrester type 1 - FLT 35 CTRL-4.0/I - 2801636
Technical data
Connection data
Conductor cross section flexible
Conductor cross section solid
Conductor cross section AWG
2.5 mm² ... 25 mm²
2.5 mm² ... 35 mm²
6 ... 2
Standards and Regulations
Standards/regulations
IEC 61643-11 2011
EN 61643-11 2012
Drawings
Dimensional drawing
88,6
17,6
Circuit diagram
66,2
58,7
L/N( )
L/N( )
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
11/15/2016 Page 3 / 3